Atp32U03 - ClimateMaster ATM11C11 Submittal Data

Table of Contents

Advertisement

Thermostat Submittal Data

ATP32U03

Wiring:
Single Stage Units
Connection to CXM Control
ATP32U03 Thermostat
Y1
Compressor
Reversing Valve
O
Fan
G
24Vac Hot
R
24Vac Common
C
L
Fault LED
Connection to DXM Control
ATP32U03 Thermostat
Y1
Compressor
Y2
Reversing Valve
O
Fan
G
24Vac Hot
R
24Vac Common
C
Fault LED
L
Single stage unit with PSC or belt drive fan motor
Note 1: Y2 may be used for High Speed fan for units with direct drive motor
Optional Wiring for AST06
ATP
GND
OD
GND TEMP SW LED
ID
GND
ASW06
(Indoor Wall Sensor)
Optional Wiring for AST008C
ATP
GND
(Locate
Indoor)
OD
ID
AST008C
GND
Note: AST or ASW can be mounted up to 200 feet
from thermostat - use minimum two-conductor 22AWG
thermostat wire. Follow all NEC and local electrical codes.
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC204 - 8
CXM
P1
Y
O
G
R
C
AL1
DXM
P1
Y1
Note 1
Y2
O/W2
G
R
C
AL1
(Locate
Outdoor)
AST008C
Rev.: 28 February, 2013
Eng/I-P
Three Heat / Two Cool
Manual / Auto Changeover
Programmable (7 Day)
Units With ECM Fan
Connection to ECM Control
ATP32U03 Thermostat
Compressor
Y1
Compressor Stage 2
Y2
O
Reversing Valve
G
Fan
24Vac Hot
R
24Vac Common
C
Fault LED
L
Units with CXM or DXM board and ECM fan motor
Two Stage Units
Connection to CXM Control
ATP32U03 Thermostat
Compressor
Y1
Compressor Stage 2
Y2
Reversing Valve
O
Fan
G
24Vac Hot
R
C
24Vac Common
L
Fault LED
Two compressor unit with CXM boards
Connection to DXM Control
ATP32U03 Thermostat
Compressor
Y1
Compressor Stage 2
Y2
Reversing Valve
O
Fan
G
R
24Vac Hot
24Vac Common
C
L
Fault LED
Two compressor unit with DXM boards
Field Wiring
Factory Wiring
See equipment wiring diagrams
for more details.
ECM
Y1
Y2
O
G
R
C
AL1
CXM 1
P1
CXM 2
Y
P1
Y
O
G
O
R
G
C
R
AL1
C
AL1
DXM 1
DXM 2
P1
P1
Y1
Y1
Y2
Y2
O/W2
O/W
G
G
R
R
C
C
AL1
AL1
COM 1
COM 1
S
S
C
C
Page ______ of ______

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ata11u03Ata22u01Atp21u01Atp32u03Atp32u04Ast008c

Table of Contents