Atm11C11 - ClimateMaster ATM11C11 Submittal Data

Table of Contents

Advertisement

3.00 in
[76mm]
1.25 in Depth
(32mm)
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC204 - 3
Thermostat Submittal Data
4.70 in
[119mm]
Fan: Sets fan to
continuous ON or AUTO
Temperature
increase & decrease
Mode: Selects system mode -
OFF, HEAT, or COOL
Rev.: 28 February, 2013
One Heat / One Cool
Manual Changeover
Non-Programmable
Application:
The ATM11C11 thermostat provides single-stage, non-
programmable temperature control for 24V water-source
heat pump systems.
Features:
• Color: White
• Integral switches control system and fan mode.
• Vented cover for improved temperature sensing.
• Mount directly on wall or horizontal outlet box using
mounting plate.
• Electronic sensing (no mercury bulb or bi-metal
switching).
Specifi cations:
Electrical Rating:
• Voltage 20 to 30 VAC
• Heating: 0.18 to 1.0A at 30VAC maximum.
• Cooling: 1.5A running, 7.5A inrush at 25 VAC.
Temperature Settings:
• Scale Range: 50°F to 90°F (10°C to 32°C).
Switching Action:
• Accurate electronic sensing/switching.
• 4-wire control of heating/cooling/reversing valve.
Wiring:
Connection to CXM Control
ATM11C11 Thermostat
Y
Compressor
W
Reversing Valve
O
Fan
G
24Vac Hot
R
Connection to DXM Control
ATM11C11 Thermostat
Y
Compressor
W
O
Reversing Valve
G
Fan
24Vac Hot
R
Eng/I-P

ATM11C11

CXM
Y
O
G
R
DXM
Y1
O/W2
G
R
Page ______ of ______

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ata11u03Ata22u01Atp21u01Atp32u03Atp32u04Ast008c

Table of Contents