Atp32U04 - ClimateMaster ATM11C11 Submittal Data

Table of Contents

Advertisement

Thermostat Submittal Data

ATP32U04

Wiring:
Units with ClimaDry Reheat
Connection to DXM Control (PSC Fan)
ATP32U04 Thermostat
Y1
Compressor
DH
Dehumidification
Reversing Valve
O
Fan
G
24Vac Hot
R
24Vac Common
C
Fault LED
L
Electric Heat
W1
Single stage unit with ClimaDry Modulating Reheat Option and PSC fan
Connection to DXM Control
ATP32U04 Thermostat
Y1
Compressor
Compressor Stage 2
Y2
Dehumidification
DH
Reversing Valve
O
Fan
G
24Vac Hot
R
24Vac Common
C
Fault LED
L
W1
Electric Heat
Two-stage unit with ClimaDry Modulating
Reheat Option and DXM board
Field Wiring
Factory Wiring
Optional Wiring for AST06
ATP
GND
OD
GND TEMP SW LED
ID
GND
ASW06
(Indoor Wall Sensor)
Note: AST or ASW can be mounted up to 200 feet from thermostat - use minimum two-conductor 22AWG thermostat
wire. Follow all NEC and local electrical codes.
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC204 - 10
DXM
P1
Y1
H
O/W2
G
R
C
AL1
W
DXM
P1
Y1
Y2
H
O/W2
G
R
C
AL1
W
See equipment wiring diagram for more details
Rev.: 28 February, 2013
Eng/I-P
Three Heat / Two Cool
Auto / Manual Changeover
Programmable (7 Day)
With Humidity Control
Units with ECM Fan
Connection to ECM Control
ATP32U04 Thermostat
Y1
Compressor
Compressor Stage 2
Y2
Dehumidification
DH
Reversing Valve
O
Fan
G
24Vac Hot
R
24Vac Common
C
Fault LED
L
W1
Electric Heat
Units with CXM or DXM board and ECM fan motor, utilizing
ECM dehumidification mode (w/o ClimaDry option)
Notes:
1) ECM dehumidification mode slows down fan speed in the
cooling mode when dehumidification output from thermostat is
active. Normal heating and cooling fan speeds are not
affected.
2) ECM board DIP switch SW9 must be in dehumid. mode.
Optional Wiring for AST008C
ATP
GND
(Locate
Indoor)
OD
ID
AST008C
GND
ECM
Y1
Y2
DH
O
G
R
C
AL1
W
(Locate
Outdoor)
AST008C
Page ______ of ______