Ata11U03 - ClimateMaster ATM11C11 Submittal Data

Table of Contents

Advertisement

Thermostat Submittal Data

ATA11U03

Mode: Selects system mode -
OFF, HEAT, COOL, or AUTO
4.12 in
[105 mm]
1.12 in Depth
(28 mm)
Back Plate:
2.88 in
[73 mm]
.50 in
3.25 in
[13 mm]
[83 mm]
4.40 in
[118 mm]
Application:
The ATA11U03 electronic thermostat provides single-stage,
2 fan speed selections, non-programmable temperature
control for 24 Vac water-source heat pump systems.
Features:
• Heat-Off-Cool-Auto System selections.
• Fan Low or High selections.
• Fan-On-Auto selections.
• °F or °C temperature display.
• Backlight user select.
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC204 - 4
5.12 in
[130 mm]
Temperature
increase / decrease
Fan: Selects continuous fan OFF or
ON and High Speed or Low Speed
Mounting
Holes
3.56 in
[90 mm]
Rev.: 28 February, 2013
Eng/I-P
One Heat / One Cool
Auto / Manual Changeover
Non-Programmable
Features (cont.):
• Installer setup options allow for customized
applications, including dead band adjustment,
temperature display offset, manual heat-cool only,
keypad lockout, sensing on board or remote,
maximum cycles per hour, fan speeds (2 or 1), setting
minimum cooling temperature, and setting maximum
heating temperature.
• Zero temperature droop performance.
• Setpoints are permanently held in memory (no
batteries used) and retained during power outages.
• Backplate wiring for easy installation.
Specifi cations:
Electrical Rating:
• Input Power: 18 to 30 Vac, 50/60 Hz.
Temperature Settings:
• Setpoint Range: 50°F to 90°F [10°C to 32°C].
• The default setpoint for heating is 68°F [20°C] and
for cooling is 78°F [25.5°C]. Press the
to change the setting. To change between heat,
cool, and auto settings, press the mode key until the
desired setting appears.
Output Ratings:
• Maximum current for each output is 1 Amp, 3 Amp total.
Wiring:
THERMOSTAT
Rc
Rh
W
C
G
NOTE 1
G2
S2
NOTE 2
S1
O
Y1
1. For units using only 1 speed (see unit wire diagram.) Must
add jumper on thermostat between G and G2, or confi gure
thermostat for 1 speed (G only).
2. For optional remote sensor, confi gure thermostat remote
sensing, use ASW06 (wall sensor) or 17B0008N05 (duct sensor).
keys
▲ or ▼
HEAT PUMP
CXM/DXM
R
W OR W1
C
G
H (DXM ONLY)
O
Y or Y1
Page ______ of ______

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ata11u03Ata22u01Atp21u01Atp32u03Atp32u04Ast008c

Table of Contents