Atp32U03 - ClimateMaster ATM11C11 Submittal Data

Table of Contents

Advertisement

6.25"
[159mm]
4.25"
[108mm]
1.25" Depth
[32mm]
Mounting:
UP
1.50"
3.25"
[38mm]
[83mm]
Application:
The ATP32U03 Thermostat provides 3 stages heating,
2 stages of cooling, and programmable temperature
control of 24V water-source heat pump equipment.
Features:
• 7-day programming.
• Four periods per day.
• ºF or ºC temperature display
• 12 or 24 hour clock.
• Individual heat and cool setpoints.
• Zero temperature droop performance.
• Automatic (program mode) or manual
(HOLD) operation.
• Night Setback mode initiated by an external signal
(when using a DXM controller).
• Convenient overrides allow temporary setpoint changes.
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC204 - 7
Thermostat Submittal Data
.62"
[16mm]
3.00"
[76mm]
0.62"
[16mm]
Rev.: 28 February, 2013
Three Heat / Two Cool
Manual / Auto Changeover
Programmable (7 Day)
Features (cont.):
• Setpoints are permanently held in memory (no
batteries used) and retained during power outages.
• Room temperature offset adjustment.
• Progressive Recovery anticipates the time required to
bring the space temperature to the next programmed
event, and brings on the heat pump accordingly.
• Large backlit dot matrix display is activated whenever
a key is pressed and remains on for 25 seconds.
• Menu-driven programming with five navigation buttons
(UP/DOWN/LEFT/RIGHT/SELECT) for ease of use.
• Fault indication with red backlight display.
• Configurable service interval messages and servicing
contractor contact information.
• Keypad lockout.
• Back-plate wiring connections for easy installation.
• Exclusive fault identification (When used with CXM
or DXM) displays fault from CXM/DXM board (e.g.
condensate overflow) and suggests possible causes.
• Compatible with optional AST008C sensor for use
as remote and/or outdoor sensor, for indoor wall-
mounted remote sensor use ASW06.
• Automatic fan staging (when used with DXM board
and direct drive motor).
Specifi cations:
Electrical Rating:
• Input Power: 18 to 30 VAC, 50/60 Hz.
Operating Conditions:
• 32ºF to 104ºF [0ºC to 40ºC].
• 10% to 95% non-condensing.
Temperature Settings:
• Setpoint range: 55ºF to 95ºF [12ºC to 35ºC], +/- 2ºF [1ºC].
Output Ratings:
• Maximum current for each output is 1.0 Amp (2.0 max.
output total).
Eng/I-P

ATP32U03

Page ______ of ______

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ata11u03Ata22u01Atp21u01Atp32u03Atp32u04Ast008c

Table of Contents