To Connect The Refrigerant Piping To The Indoor Unit - Daikin FTXP20N5V1B Installer's Reference Manual

Split system air conditioners
Hide thumbs Also See for FTXP20N5V1B:
Table of Contents

Advertisement

7.2.6 To connect the refrigerant piping to the indoor unit

FTXP20~35N5V1B + ATXP20~35N5V1B
Split system air conditioners
4P519439-20U – 2022.09
a
a Flare's inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
Pipe length. Keep refrigerant piping as short as possible.
1 Connect refrigerant piping to the unit using flare connections.
2 Insulate the refrigerant piping, interconnection cable and drain hose on the
indoor unit as follows:
c
a
b
f
a Gas pipe
b Gas pipe insulation
c Interconnection cable
d Liquid pipe
e Liquid pipe insulation
f Finishing tape
g Drain hose
NOTICE
Make sure to insulate all refrigerant piping. Any exposed piping might cause
condensation.
b
c
d
e
g
7
Piping installation
|
Installer reference guide
37

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents