Configuration Wiring

To configure the HMI using the EZwarePlus software, use the Ethernet
Configuration Cable (P/N 7431-0104) or USB Configuration Cable (P/N
7431-0119).
HMI Model
HMI5040B, HMI5070B
HMI5040BN, HMI5070BN,
HMI5100BN
Ethernet
If using a switch or router between the PC and the HMI, use a straight-
through or crossover cable as required by the switch or router.
In order to download a project to the HMI over Ethernet, the HMI must be
assigned a unique IP address that is on the same subnet as the
development PC.
Follow these steps to enter the System Settings menu and assign the
HMI an IP address:
1. Apply power to the HMI.
2. Click the arrow icon located in the lower-right corner of the screen.
3. Click the gear icon to enter the system settings menu
4. When prompted, enter the system password (default: 111111).
5. Navigate to the Network tab.
6. Enter the desired IP address, or select Obtain an IP Address
Automatically to enable DHCP.
7. Click Apply to save the changes, and OK to exit the system settings
menu.
8. The updated IP address will appear in the system information
window, also accessed via the arrow icon. For more information on
Ethernet configuration options, please refer to the EZwarePlus
Programming Manual.
1010-1051 Rev 00
HMI5000B Installation Guide
Configuration Cable
P/N 7431-0104
Ethernet
(Crossover)
X
P/N 7431-0119
Micro USB
X
www.maplesystems.com