Huawei UPS5000-E-600 kVA Quick Manual page 13

Table of Contents

Advertisement

2. Set the language, time, date, network parameters, and system parameters on the Settings
Wizard screen.
3. After you perform the settings, the Bypass mode
and No battery alarms are reported by the MDU
and do not need to be cleared. If there is any
other alarm, you need to rectify the fault.
4. If the system has connected to the remote EPO switch, you need to choose Monitoring > UPS
System > Running Parameter > System Settings on the WebUI and set EPO detection to
Enable.
5. View the system running status diagram on the MDU to check that the UPS is working in
bypass mode.
5.3
Starting inverter
1. On the main menu, choose Common Functions and tap Inv. ON.
2. In the displayed login window, enter the user name and password, and tap
3. In the displayed dialog box, tap Yes to start the inverter.
System User
admin (system administrator)
operator (common user)
LCD Preset
WebUI Preset
Password
Password
000001
Changeme
000001
Changeme
13
.
To ensure system security,
change the LCD and
WebUI passwords after
the first login.