Tripp Lite SmartOnline S3MX Owner's Manual page 52

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
8. Specifications
MODELS
EXTERNAL BATTERIES (S3M60KX/KXD*, S3M80KX/KXD* require external batteries for backup. S3M30KX-NIB/KXD-NIB*,
S3M40KX-NIB/KXD-NIB* [without internal batteries installed], require external batteries for backup).
Type
DC Nominal Acceptance Voltage
Quantity
Maximum Charging Current
Float Voltage
Boost Charging
End of Discharge
Charger Temperature Compensation
PHYSICAL
Dimensions (H x W x D)
Unit Weight (With Internal Batteries)
Unit Weight (Without Internal Batteries)
ENVIRONMENT
Operating Temperature
Storage Temperature
Operating Humidity
Operating Altitude
Audible Noise
Heat Dissipation (100% Load)
Heat Dissipation (50% Load)
MANAGEMENT
Network Management Interface
Control Panel
Contact Closure Interface
Remote Emergency Power Off (REPO)
RS-232
STANDARDS
Safety
EMC/EMI
Ingress Protection Rating
CE Marking
RoHS Compliant
Quality Management System
OTHER INFORMATION
Colour
Mobility
ACCESSORIES (Sold Separately)
Scalable Battery Cabinets
Network Management Card
Battery Temperature Compensation
Thermostat Kit
Remote Environmental Sensors
(Require WEBCARDLX.)
Contact Closure Card
External Bypass Panel
Scalable Charger Board Kits
* "KXD" and "KXD-NIB" models are dual-AC input capable.
S3M30KX/KXD*
S3M40KX/KXD*
12V Non-Spillable VRLA AGM/GEL
Adjustable up to 4A ± 10%
(Max 12A with 2 x CBKIT30-40.)
1000 x 300 x 815 mm
265 kg
60 kg
0 to 40˚ C (≤ 25˚ C for optimal battery lifespan.)
0 to 35˚ C (UPS with Batteries), -15 to 60˚ C (UPS without Batteries)
< 1000 m (Derate output power by 1% per 100 m above 1000 m.)
< 60 dBA at 1 m
5527 BTU/h
7362 BTU/h
2994 BTU/h
3992 BTU/h
Requires optional WEBCARDLX. (Monitor, control and reboot the UPS using HTML5 web,
SSH/telnet and SNMP interfaces. Supports centralised management through integration
with a wide range of Network Management Systems and DCIM platforms.)
62 mm LCD with supplemental LEDs.
Requires Optional RELAYCARDSV Programmable Relay I/O Card
Feature Included (Default: Normally Closed)
IEC 62040-1:2008+A1:2013 (TUV Approval)
EN 62040-2:2006 (Category C3) (TUV Approval)
Available models include BP480V100-NIB, BP480V100, BP480V65-NIB, BP480V65,
BP480V40-NIB, BP480V40, BP480V10-NIB, BP480V10, BP480V09.
WEBCARDLX (Monitor, control and reboot the UPS using HTML5 web, SSH/telnet and
SNMP interfaces. Supports centralised management through integration with a wide range
of Network Management Systems and DCIM platforms.)
MODBUSCARDSV (Modbus protocol via RS-485 interface.)
E2MT (Temperature Sensor); E2MTDO (Temperature Sensor with Digital Outputs);
E2MTDI (Temperature Sensor with Digital Inputs);
E2MTHDI (Temperature/Humidity Sensor with Digital Inputs)
Contact your local sales representative or distributor for more information.
CBKIT30-40 (Adds 4A; Max 2)
52
S3M60KX/KXD*
± 240 VDC
40N (N ≥ 1 x Strings of 20 + 20)
Adjustable up to 8A ± 10%
(Max 24A with 2 x CBKIT30-80.)
13,65V/Battery; 2,27V/Cell
14,1V/Battery; 2,35V/Cell
10V/Battery; 1,67V/Cell
N/A
316 kg
N/A
61 kg
108 kg
0 to 95% (Non-Condensing)
< 70 dBA at 1 m
11054 BTU/h
5998 BTU/h
Included (Service Only)
IP20
Yes
Yes
ISO 9001
RAL 9005 Jet Black
Casters
(NIB=No internal batteries.)
RELAYCARDSV
CBKIT30-80 (Adds 8A; Max 2)
S3M80KX/KXD*
1010 x 360 x 790 mm
N/A
113 kg
< 75 dBA at 1 m
14738 BTU/h
7984 BTU/h

Advertisement

Table of Contents
loading

Table of Contents