3. Installation and Setup
27) Use the Battery Fuse PCB to connect batteries and refer to the Figures 3.5, 3.6 and 3.7. Refer to Table 3.1 for a complete battery
wiring listing.
BAT +1
cable to positive pole of #40 battery.
BAT +2
cable to positive pole of #80 battery.
BAT N1
cable to positive pole of #20 battery.
BAT N3
cable to positive pole of #60 battery.
BAT +1
Left Side
S3M30KX/S3M30KXD
S3M40KX/S3M40KXD
Figure 3.5
BAT -2
Notes:
• The blue numbers in above figures are "Battery Numbers" from 1 to 80, which are used for battery position identification.
• There are 2 red wires, 2 black wires and 4 blue wires, which connect the battery fuse board and batteries.
• S3M30KX/KXD/NIB battery fuse board part number: 71-303365-XXG.
• S3M40KX/KXD/NIB battery fuse board part number: 71-303366-XXG.
BAT +2
* Only the BAT -2 cable and connector is routed through the cable grommet.
Battery Fuse PCB
Input BAT-1
BAT N1
BAT N3
Figure 3.7
BAT -1 cable to negative pole of #1 battery.
BAT -2 cable to negative pole of #41 battery.*
BAT N2
cable to negative pole of #21 battery.
BAT N4
cable to negative pole of #61 battery.
BAT -2*
Right Side