Tripp Lite SmartOnline S3MX Owner's Manual page 40

3-phase ups systems
Hide thumbs Also See for SmartOnline S3MX:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
4. Operation
20: Output-C Voltage Calibration
Interface
21: Current Charger Setting
Interface
22: Charging Boards Number Setting
Interface
23: Redundancy setting
Interface
Setting
Parameter 2: Always shows OP.V as output voltage.
Parameter 3: Shows the internal measurement value of the output-C voltage. You can calibrate
it by pressing Up or Down according to the measurement from an external voltage meter. The
calibration result will be effective by pressing Enter. The calibration range is limited within +/-9V.
This function is normally used for parallel operation.
OP.U
*It will display number 2 under
Setting
Parameter 2: CHG indicates adjust charger current function.
Parameter 3: Set the charger current. The setting range is 1A to 4A. The default value is 2A for
30K/40K and 4A for 60K/80K.
• 30K-40K: Adjust the charger current function only for one charger board installed on UPS. This
feature will not work when more than one charger board is installed.
• 60K-80K: Adjust charger current function for only two charger boards installed on UPS. This
feature will not work when more than two charger boards are installed.
Note: Once the charger board is extended, all installed charger boards will charge the battery at the maximum
power of 4A current. Extension board kits are available for the S3M30KX and S3M40KX models (CBKIT30-40)
and the S3M60KX and S3M80KX models (CBKIT30-80).
Setting
Parameter 2: CHG indicates adjust charging boards quantity function.
Parameter 3: Set the charging boards quantity. The setting range is from 1 to 3 and the default
value is 1.
• 60K-80K: Two charger boards are one group. If the UPS installs four charger boards, it needs to
be set to 2. If the UPS installs six charger boards, it needs set to 3.
Note: Once the charger board is extended, this parameter has to be changed accordingly.
Setting
Parameter 2: TOL it indicates the quantity of UPS. The setting range is from 1 to 3 and the
default value is 1.
Parameter 3: RED it indicates the quantity of redundant UPS. The setting range is from 0 to 2
and the default value is 0.
Note: The setting quantity of each UPS needs to equal the quantity of the UPS connected in parallel for
redundancy. If setting quantity is not equal to the quantity of UPS in the system, the UPS will generate a warning.
to represent the output C voltage.
40

Advertisement

Table of Contents
loading

Table of Contents