Sample Connection; Line / Load Connection - Siemens SINAMICS S120 Equipment Manual

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.3.3.2

Sample connection

Fig. 4-18
4.3.3.3

Line / load connection

Table 4-9
Line / load connection for the Active Line Module
Terminals
U1, V1, W1
3-phase AC power input
DCP, DCN
DC power output
PE connection
Chassis Power Units Liquid Cooled
SINAMICS S120 Equipment Manual, Edition 12/2007, 6SL3097-2AM00-0BP4
+
ext.
24 V DC
M
to Active
Interface Module
from Active
Interface Module
Terminal connection diagram for the Active Line Module
Technical specifications
Voltage:
380 V 3 AC, –10% to 480 V 3 AC, +10% (-15% < 1 min)
500 V 3 AC, –10% to 690 V 3 AC, +10% (-15% < 1 min)
Connection lugs: d = 13mm (M12 / 50Nm) for ring cable lugs to DIN 46234
Voltage:
570 to 720 V DC
750 to 1035 V DC
Connection lugs: d = 13mm (M12 / 50Nm) for ring cable lugs to DIN 46234
Connection lugs: d = 13mm (M12 / 50Nm) for ring cable lugs to DIN 46234
Active Line Module
X9
1
+24 V
2
M
3
Bypass contactor
4
control
5
Pre-charging
6
contactor control
7
EP +24 V
8
EP M1
X41
4
not assigned
3
not assigned
2
EP +24 V
1
EP M1
Line Modules
4.3 Active Line Modules
X400
X401
X402
DCP
DCN
H200 (Ready)
H201 (DC Link)
4-25