Event Counter Cntggio; Identification; Application; Setting Guidelines - ABB Relion 650 Series Applications Manual

Transformer protection
Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 15
Monitoring
Table 33:
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
15.5

Event counter CNTGGIO

15.5.1

Identification

Function description
Event counter
15.5.2

Application

Event counter (CNTGGIO) has six counters which are used for storing the number of times
each counter has been activated. CNTGGIO can be used to count how many times a specific
function, for example the tripping logic, has issued a trip signal. All six counters have a
common blocking and resetting feature.
15.5.3

Setting guidelines

Operation: Sets the operation of Event counter (CNTGGIO) On or Off .
15.6

Disturbance report

15.6.1
Identification
Function description
Disturbance report
Analog input signals
Analog input signals
Analog input signals
Table continues on next page
226
General settings parameters for the Measurement function
Short description
Operation
Off / On
Amplitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & U
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, U and I
© Copyright 2011 ABB Power Grids. All rights reserved
Selected
Comment
value
On
Function must be
1.000
Typically no scaling is required
180.0
Typically no angle compensation is required.
However here the required direction of P & Q
measurement is towards busbar (Not per IED
internal default direction). Therefore angle
compensation have to be used in order to get
measurements in aliment with the required
direction.
L1L2
Only UL1L2 phase-to-phase voltage is
available
0.00
Typically no additional filtering is required
IEC 61850
IEC 60617
identification
identification
CNTGGIO
S00946 V1 EN-US
IEC 61850
IEC 60617
identification
identification
DRPRDRE
-
A1RADR
-
A2RADR
-
A3RADR
-
1MRK 504 124-UEN B
On
ANSI/IEEE C37.2
device number
-
ABBD8E209025 v3
GUID-2586E309-290A-43D7-A15E-7CB8DEDEBC85 v2
ANSI/IEEE C37.2
device number
-
-
-
-
Transformer protection RET650
Application manual
M14884-1 v4
M13408-3 v3