Popit Labels; D8128D Octopopit Module; Description; Listings - Bosch D7212GV3 Operation And Installation Manual

Hide thumbs Also See for D7212GV3:
Table of Contents

Advertisement

.

Figure 14: Program Record Sheet

9.3.8

POPIT Labels

D7212GV3 off-board points are numbered 9 to 40.
Two sheets of peel-off POPIT labels are supplied with
the D8125 POPEX Module. Use the sheet marked
"Bank1" for Points 9 to 40.
Each label has two parts. Place the smaller part, with
only the point number, on the chip. Place the larger
part, with the switch settings, on the base of the
POPIT. Set the switches and cover the POPIT.
Do not program two POPITs for the same point
number. After programming all the points, perform a
Service Walk Test. Refer to Section 4.10 Service
Walk Test on page 17. If a point does not test, check
the programming for a duplicated address.
Walk Test and Service Walk Test Do Not Show
Extra Points: If the point assignment switches on a
POPIT or OctoPOPIT are set incorrectly, missing and
extra point conditions might occur. If the same point
number is assigned to two or more POPITs or
OctoPOPITs, none of the points with that number test
correctly. Refer to Section 9.1 Point (Zonex) Bus:
D7212GV3 Terminals on page 32.
Bosch Security Systems, Inc. | 10/10 | F01U143079-03
D7212GV3 | Operation and Installation Guide | 9.0
9.4

D8128D OctoPOPIT Module

9.4.1

Description

The D8128D OctoPOPIT Module combines the
functions of the D8125 POPEX Module and the
D9127 POPIT Modules to provide eight off-board
points in a single module. You can wire both D8128D
OctoPOPIT and D8125 POPEX Modules in parallel to
the Zonex bus terminals on the same control panel.
Review Section 6.0 Power Outputs on page 24 to
ensure that there is enough power for the
OctoPOPITs and other powered devices that will be
connected to the system.
Up to four D8128Ds can be connected to the
D7212GV3 Control Panel (three points can be used
on the last OctoPOPIT).
9.4.2

Listings

The D8128D OctoPOPIT Module is UL Listed for
Local or Police Connected Burglary Alarm, Central
Station Burglary Alarm, Household Burglary Alarm
applications, and commercial fire applications (UL 864
and NFPA 72).
Modules D8128, D8128A, or D8128B are
incompatible with the D9412GV3 or
D7412GV3. Use only the D8128D
OctoPOPIT Module. Using Modules D8128,
D8128A, or D8128B can cause intermittent
Missing and Restoral Reports.
Off-Board Points
37