6.2. General display parameters

Parameter
SEC
GLM
dI.HI
dI.Lo
tASt
FLAS
SEC: Measurement timet
Setting the base measuring time or the frequency filter for calming the measured value. This filter
value can be set from 0.01...2.00 seconds. For impulse measurements, the value can be selected
up to 0.00, so that the detection runs at the maximum speed.
GLM: sliding averaging
In addition to the measuring time, a sliding average of 1...20 values can also be activated. Here,
no separate weighting takes place between the past values. With GLM = 1 the sliding averaging
is switched off.
dI.Lo, dI.HI: Initial value representation / final value representation in the display
For overflow evaluation, the measuring range and the optionally selected overflow behavior are
(OVEr) evaluated. In addition to this, this range can be further narrowed down by the two
parameters dI.HI and dI.Lo .
tASt: Assignment (deposit) of key functions
Here, either a min/max value query or a limit value correction can be stored on the direction keys
for the operating mode. If the min/max memory is activated with EHtr, the measured min/max
values are stored during operation and can be queried via the [▲] [▼] direction keys. The values
are lost when the device is restarted. If you select the limit value correction AL.LI , you can
change the values of the limit values during operation without interfering with the operating
sequence. If no has been parameterized, the direction keys [▲] [▼] have no function in the
operating mode.
FLAS: Display flashes when limit value is undershot / limit value exceeded
Here, a display flashing can be used as an additional alarm function either to the first limit value
(Selectionl: AL-1), to the second limit value (Selectionl: AL-2) or to both limits (Selection: AL-12)
be added. With no (Factory setting) no blinking is assigned.
Selection option
to
to
to
to
27
6. Parameterization
Default