6. Parameterization
OVEr: Overflow and underflow behavior
The overflow / underflow of the measuring input is displayed with 4 bars at the top or 4 bars at the
bottom. The exception is the input type "4-20" (mA) where a measured value smaller than 1 mA is
already considered as underflow. This is to indicate a sensor failure.
No additional range check takes place here. If the display range is left, the display
no
simply remains at the lowest value "dI.Lo" or highest value "dI.HI".
If the display range "dI.Lo" / "dI.HI" is exceeded / undershot, overflow / underflow is
AdC
displayed.
The measuring signal must be exactly in the specified measuring range
rAnG
"EnD"/"OFFS" so that no overflow is detected. The display and transducer range is
additionally monitored.
The measuring signal is monitored for ±5% of the set measuring range. The display
5 Pr
range is additionally monitored.
The measuring signal is monitored for ±10% of the set measuring range. The
10 Pr
display range is additionally monitored.
SPC.A: Number of additional support points.
5 additional supporting points can be defined for the start and end values in order to linearize
non-linear sensor values. Only the activated support point parameters are displayed.
dIS1...dIS5: Display values for support points.
Under this parameter, the support points are defined in value terms.
INP1...INP5: Analog values for support points.
The supporting points are always preset according to the selected input signal ma/V. Here the
desired analog values can be freely parameterized in ascending order.