Maintenance Check List
Maintenance should be performed 1-2 times per year.
1. Remove all debris from the bottom of the pit and the
pump strainer.
2. Remove all debris floating in the water.
3. Remove all debris from the float switch and lift rod.
4. Remove all debris around the air bleed hole.
5. Fill the pit with water. Make sure pump turns on at
the intended level.
6. While the pump is running, make sure pump is
evacuating water at a good pace.
7. While the pump is running, make sure a stream of
water is escaping from the air bleed hole. If not,
clear the hole of any deposits or debris.
Troubleshooting
(Always unplug the pump from the controller before performing any maintenance)
The pump will not start or run
Thermal protector tripping or
not functioning
Pump starts and stops too
frequently
Pump will not shut off
Insufficient or no water
volume
Abnormal sound or vibration
*Consult a licensed electrician.
If the above solutions do not solve the problem, contact Glentronics customer service 800-991-0466, option 3.
Backup Installation
When the power goes out, the Basement Watchdog AC
sump pumps will not operate. For protection during a
power outage, a Basement Watchdog battery backup
system can be installed. There are three systems with
matching batteries that will provide protection.
The illustration at right is an example of a typical
battery backup installation.
Pump is not plugged in
Water is not high enough to activate the pump
Open circuit
Poor power source
Low voltage
Bad power cable
Locked impeller
Defective float switch
Defective pump
Locked impeller
Incorrect power supply
Overburdened due to heavy sand content in the water
Pump running continuously with no water present
Float stops are positioned too close together
Water flowing back from pipe
Clogged or frozen discharge
Blocked intake
Float switch is obstructed and can not drop down
Check valve installed with no air bleed hole in
pipe or pump
Check valve is stuck or installed upside down
Check valve on secondary pump will not close
and water re-circulates within the system
Partially blocked impeller
Clogged or frozen discharge
Broken or leaking pipe
Low power voltage
Check valve installed with no air bleed hole in
pipe or pump
Check valve is stuck or installed upside down
Pump is air locked
Check valve on secondary pump will not close
and water re-circulates within the system
Blocked intake
Broken impeller
Visit our website
www.basementwatchdog.com
for more information about
the Basement Watchdog AC
sump pumps and battery
backup sump pump products.
Plug pump in properly (see instructions)
Make sure float switch is positioned properly
Check circuit breaker or fuse
Check circuit line wires and cable*
Check line wires and source voltage*
Replace with new cable*
Remove strainer and clear obstruction
Replace float switch with new float switch
Replace pump with new pump
Remove strainer and clear obstruction
Check power supply source and voltage
Use water filter or replace with a higher wattage pump
Check float switch
Adjust the stopper on the lift rod
Install or replace check valve
Clear blockage or thaw frozen line
Clear debris from intake
Clear debris from the float and lift rod
Drill a bleed hole in the discharge pipe, or clean debris from the existing hole
in the pipe or pump
Reverse or replace check valve. Make sure the check valve is installed with the
flow arrow pointing up and out of the pit.
Replace the check valve on the secondary pump
Clear obstruction
Clear blockage or thaw frozen line
Repair piping
Check power voltage, wires and cable condition
Drill a bleed hole in the discharge pipe, or clean debris from the existing hole
in the pipe or pump
Reverse or replace the check valve. Be sure check valve is installed with flow
arrow pointing up and out of the pit
Remove debris from the air relief valve
Replace the check valve on the secondary pump
Clear debris from intake
Replace impeller with new one
3
FLOOR
JOIST
SLOPE
PIPES
DOWN
BACKUP SYSTEM
AC
CONTROL UNIT
OUTLET
FLOAT
PUMP
WIRE
WIRE
CHECK
VALVE
CHECK
VALVE
BATTERY
CABLE
BATTERY
PIT COVER
DRAIN TILE
AIR BLEED
BACKUP PUMP
HOLE
FLOAT SWITCH
AIR BLEED
MAIN A/C PUMP
HOLE
VERTICAL
FLOAT SWITCH
MAIN
BATTERY
A/C PUMP
BACKUP PUMP
BRICKS
BRICKS

Advertisement

loading

This manual is also suitable for:

Basement watchdog si-50v