Emerson 1552WU Reference Manual page 30

Smart wireless gateway
Table of Contents

Advertisement

Section 4: DeltaV Ready
April 2015
Figure 4-3. Gateway Context Menu (Right Click)
Now the Gateway and wireless devices are fully commissioned and available to use in other
DeltaV applications. When new devices are added to the wireless network, they will need to be
assigned to DeltaV channels through the reconcile process (right click on Gateway and select
configure IO).
Note
Logging in to the Gateway is not possible using the default TCP/IP network setting. If the
Gateway is decommissioned, use an IP address 10.5.255.254. If the Gateway is commissioned,
right click on the Gateway in DeltaV Explore and select Wireless Gateway Web Interface.
24
Reference Manual
00809-0100-4052, Rev AA
DeltaV
Ready

Advertisement

Table of Contents
loading