10. TECHNICAL DATA
Type voltage
S..H1
S..HRL1
Mains frequency
Load description
Operating modes Name
Digital set points inputs (connection signals)
Relay outputs using type 1S...H RL1
Changer, contact material: AgSnO2 / Au plated
The relay can be used for low load circuits (> 5 V 20 mA), however
not if it has been pre-loaded by 230 V AC.
Maxiumum values: 250 V 6 A, 180 W, 1500 VA
Insulation strength 4 kV / 8 mm
230 Volt, 400 Volt, 500 Volt
– 57 % + 10 %;
230 Volt – 15 % + 10 %;
> 99 V with additional 24 AC/DC elektronic power
400 Volt – 15 % + 10 %;
> 172 V with additional 24 AC/DC elektronic power
500 Volt – 15 % + 10 %;
> 215 V with additional 24 AC/DC elektronic power
all models 47Hz to 63Hz;
max. frequency change 5% per half wave
ohmic load
Load signal, with digital set point = ON
1:1
all full wave (default setting)
1:2
every 2. mains full wave (DC free)
1:3
every 3. mains full wave (DC free)
1:5
every 4. mains full wave (DC free)
The Thyro-S has 2 set point inputs. The set point inputs are safely
disconnected from the mains (SELV, PELV).
Set point 1:
Logic input 0-24 V R
Set point 2:
System interface, connection from superset
automation system via optional bus module.
=6Hz;
> 3.3kΩ ON > 3 V