18
2.5.2 LOAD MONITORING
(UNDERCURRENT MONITORING)
Thyro-S ... H RL1 is suitable for monitoring loads resulting from one or
several resistances in parallel or parallel series connection.
Thyro-S detects an increase in the load resistance. The load monitoring
operates as undercurrent monitoring on absolute values and is suitable
for use in the nominal operating mode 1:1, and with limitations in the
operating modes 1:2. 1:3 and 1:5.
The load monitoring is supplied with the default configuration OFF =
left stop R205 (=0)
For all other configurations:
If the load current falls below the level set the error indication relay will
respond with a delay (4-10 sec depending on operating mode). The
result is indicated via an optionally connected bus system.
This can be set in accordance with the following table.
2.5.3 LOAD MONITORING
(OVERCURRENT MONITORING)
Along with undercurrent monitoring 2.5.2 the device also has over-
current monitoring. This can only be configured using Thyro-Tool Family.