Advanced Energy Thyro-S 1S H 1 Series Manual page 21

Table of Contents

Advertisement

NO. OF
PARALLEL
I
LOAD RESIS-
LOAD NOM
I
TANCES E.G.
TYPE/CONTROLLER
NUMBER
1
100%
1
80%
1
60%
1
40%
1
20%
2
100%
2
80%
2
60%
2
40%
2
20%
3
100%
3
80%
3
60%
3
40%
4
100%
4
80%
4
60%
4
40%
5
100%
5
80%
5
60%
5
40%
TAB. 1 LOAD MONITORING
Deviating values are to be converted by percentage. The set monitor-
ing value should always be "midpoint" between the value with load
current and the value after interruption.
NOTE
Settings above 90% and below 10% are not practical. If low load cur-
rents are required, check whether a controller with a lower type current
can be used.
RESISTANCE
INCREASE IN
/
CASE
OF FAULT
Infinite
100,0%
50%
33,3%
25,0%
RECOM-
MENDED
SETTING
POTI
FOR POTI
REVOLU-
R205
TIONS CA.
50.0%
8.5
40.0%
7
30.0%
6
20.0%
4.5
10.0%
2.5
75.0%
12
60.0%
9.5
45.0%
7.5
30.0%
6
15.0%
3.5
83.3%
13
66.7%
12.5
50.0%
9
33.3%
6
87.5%
13.5
70.0%
12.5
52.5%
9
35.0%
6
90.0%
14
72.0%
11.5
54.0%
9
36.0%
6.5
19