20

3. OPERATION

3.1 CONFIGURATION SWITCH S1

A 4-pole DIP switch is situated at the front behind the hood. The indi-
vidual switches are marked from 1-4 starting from the bottom and must
be set before operation. They are only read in once when switched on
(mains recovery). For safety reasons further operation is carried out
with the hood closed.
S1-
1
2
0
0
1
0
0
1
1
1
For operations where initially no nominal load is possible (e.g.drying)
reduced power can be controlled by Thyro-S independently.
With 1:2 operation each 2. cycle is switched, with 1:3 and 1:5 operation
half cycles are switched with alternating polarity so that while switched
on the load is supplied with d.c.-free energy.
S1-
3
Function
0
default
1
Thyro-Tool Family mode
Using the Thyro-Tool Family mode, all parameters can be configured
by software.
The following table is valid for dip-switch 4:
S1-
4
Function
0
default (resistive load)
1
resistive - inductive load (with phase angle of 1st half wave)
By switch S1-4, the Thyro-S can be adjusted to resistive – inductive
loads. This can be realized by phase angle of 1st half wave. If the
switch is closed, the value for phase angle of 1st half wave (short AN1)
can be adjusted by Thyro-Tool Family. The default value is 60°.
Operating mode
1:1 operation, nom. Oper. mode (default setting)
1:2 operation
1:3 operation
1:5 operation

Advertisement

Table of Contents
loading