Misc

Event Log

The events are always presented in four different types of event logs,
see below.
Use Extended Log:
This option is not selected as default.
1. General;
All events except Alarm, Interlocking and Web
events, see below. Max. 999 events. See also page 25.
2. Alarm; Fire alarms, Pre-warnings, Co-incidence alarms and
Alert Annunciation alarms. Max. 999 events. See also page
25.
3. Interlocking; Interlocking events. Max. 999 events. See also
page 26.
4. Web Event; Web events. Max. 100 events. See also page 26.
When this option is selected the General log is extended to max.
10000 events.
1. General; All events, including Alarm, Interlocking and Web
events. Max. 10000 events. See also page 25.
2. Alarm; Pre-warnings, Fire, heavy smoke/heat, Co-incidence'
Alert Annunciation, Delayed, Isolated, Acknowledged and
Quiet alarms. Max. 999 events. See also page 25.
3. Interlocking; Interlocking events. Max. 999 events. See also
page 26.
4. Web Event; Web events. Max. 100 events. See also page 26.
Daily Log Saving:
When this option is selected the logs
flash memory
in the Web-server at midnight every day.
(see above)