4.10
4.10.1
4.10.1.1
4.10.1.2
4.10.1.3
4.10.1.4
Operating Instructions Web512 V2.6.x for Web-server II 1598

Operation; Maintenance

NOTE! Log in on User level 2, 3 or 4 is required.
The Daily - Disablement view is default (User level 2). See page 27.
The Maintenance - Disablement view. (User level 3). See below.
The Service – Misc. view. (User level 4). See page 35.
Click Menu to get access to the following buttons:
If required, click Login and Log in on User level 3 or 4.
Click Maintenance to open the Maintenance - Disablement view.
Maintenance – Disablement
The Maintenance - Disablement view:
Control Unit Loop
Like menu H8/S2 & S3.
A specified COM Loop (0-3) in a specified Control Unit (00-29) can
be disabled / re-enabled.
BS4 Loop
Like menu H8/S2 & S3.
A specified BS4 Loop (0-3) on a specified expansion board 1584,
Autronica interface Board (0-3), in a specified Control Unit (00-29),
can be disabled / re-enabled.
DET8 Loop (Zone line input)
Like menu H8/S2 & S3.
A specified zone line input, Loop (0-7) on a specified expansion
board 1580, 8 zones expansion Board (0-5), in a specified Control
Unit (00-29), can be disabled / re-enabled.
Loop unit Loop (Loop unit zone line input)
Like menu H8/S2 & S3.
32