50
Display:
Error code:
Description:
Cause and Remedy:
Error code:
Description:
Cause and Remedy:
Error code:
Description:
Cause and Remedy:
Operating Manual
4
Negative draft input open, measuring circuit from negative draft meas-
urement open
signal incorrect
signal cable defect
signal too low
combustion chamber leak
5
Negative draft input short-circuit, measuring circuit from negative
draft measurement is shorted out
signal incorrect
signal cable defect
signal too high
6
Negative draft pressure in boiler is not achieved
negative draft tube disconnec-
ted
negative draft does not
change
Negative draft pressure
too low
check polarity and signal
(0-10V)
replace sensor
signal below 0V
check closure of boiler door
check polarity and signal
(0-10V)
replace sensor
signal above 10V
connect up negative draft
tube
Check negative draft tube for
leaks. Check flue gas tube for
blockage.
Close boiler door, check tube
to negative draft sensor, check
whether boiler flue gas outlet
is clear, check whether con-
densation heat exchanger is
clear. Make sure flue gas fan is
running.