Download Print this page
Zennio LUMENTO X4 Technical Documentation

Zennio LUMENTO X4 Technical Documentation

Rgb controller led dimming

Advertisement

Quick Links

RGB CONTROLLER
ZN1DI-RGBX4
FEATURES
Control of RGBW LED or 4 independent channels.
External power supply required (12 or 24 VDC).
LED test function.
KNX BCU integrated.
CE directive compliant.
1. KNX
2. KNX programming and
connector
internal test LED
4. Test button 5. LED control
terminal block
KNX programming button: short button press to set the programming mode. If this button is held while plugging the device into
the KNX bus, it goes into safe mode.
KNX programming and internal test LED: the red LED indicates programming mode. When the device goes into safe mode, it
blinks red every 0.5 seconds. The blinking blue LED indicates internal test.
Test button: it tests the functioning of channels connected to the device. Push and hold for 3 seconds to get in/out of the testing
mode.
Test LED and polarity: tricolored LED that indicates which channel (red=channel 1/R, green=channel 2/G, blue=channel 3/B,
qhite=channel 4/W) is being tested. Orange light indicates reverse polarity in external power supply.
GENERAL SYSTEM SPECIFICATIONS
Type of device
Voltage
Voltage range
KNX supply
Power consumption
Bus connection
External power supply
Power supply cable section
Type of control
Ambient temperature
Storage temperature
Ambient humidity
Storage humidity (relative)
Complementary characteristics
Safety class
Operation type
Device action type
Electrical solicitations period
Protection class
Assembly
Bus power failure response
Response when restarting bus
PCB CTI index
Enclosure
Size
Weight
Operation indication
© Zennio Avance y Tecnología S.L.
3. KNX programming
button
6. External
7. Test and reversed
power supply
polarity indicator LED
Electric operation control device
29V DC típicos
21...31V DC
145 mW
Typical BUS connector TP1, 0.50mm2 section
12 or 24V DC
1.5 mm² to 2.5 mm²
PWM (150, 300, 488 or 600 Hz)
0ºC to +45ºC
-5ºC to +50ºC
30 to 85% RH (no condensation)
30 to 85% RH (no condensation)
Class B
II
Continuous operation
Type 1
Long
IP20, clean environment
Independent control assembly device
Connect LUMENTO as near as possible to both, the LED to dimmer and the external power supply
Data saving
Data recovery
175 V
PC-ABS FR V0 halogen free
Without terminal blocks: 144x44x22mm / With terminal blocks: 157x44x22mm
102 g.
Programming/internal test LED indicates: programming mode (red lighting), safe mode (red
blinking) and internal test (blue blinking).
Test LED indicates: white, test channel 4 (W); red, test channel 1 (R); green, test channel 2 (G);
blue, test channel 3 (B). Reverse polarity of external power supply is indicated by the test LED with
orange light.
Edition 3
3
1
For further information
www.zennio.com
LUMENTO X4
LED DIMMING
Technical Documentation
5
4
7
2
Figure 1. LUMENTO X4
6
Page. 1 of 2

Advertisement

loading

Summary of Contents for Zennio LUMENTO X4

  • Page 1 Test LED indicates: white, test channel 4 (W); red, test channel 1 (R); green, test channel 2 (G); blue, test channel 3 (B). Reverse polarity of external power supply is indicated by the test LED with orange light. Page. 1 of 2 © Zennio Avance y Tecnología S.L. Edition 3 For further information www.zennio.com...
  • Page 2 The voltage of the power supply connected to LUMENTO will never exceed the voltage required for the load, which is specified by the manufacturer. Not following this recommendation would mean a risk for the installation. Page. 2 of 2 © Zennio Avance y Tecnología S.L. Edition 3 For further information...

This manual is also suitable for: