Technical Specifications Of The Scalance Xcm108Poe (6Gk5108-0Pa00-2Ac2) - Siemens SIMATIC NET SCALANCE XCH-100 Equipment Manual

Table of Contents

Advertisement

7.3
Technical specifications of the SCALANCE XCM108PoE
(6GK5108-0PA00-2AC2)
The following technical specifications apply to SCALANCE XCM108PoE (6GK5108-0PA00-2AC2).
Technical specifications
Connection to Industrial Ethernet
Electrical connectors
Electrical data
Power supply
1)
Current consumption
Active power at max PoE load
Thermal Design Power
Overvoltage category
Fusing
PoE power per device
Signaling contact
1)
Permitted ambient conditions
Ambient temperature
Relative humidity
Housing, dimensions and weight
Design
SCALANCE XCH-100/XCM-100
Equipment Manual, 11/2022, C79000-G8976-C662-01
7.3 Technical specifications of the SCALANCE XCM108PoE (6GK5108-0PA00-2AC2)
Quantity
Connector
Properties
Transmission speed
Rated voltage
Voltage range (incl. tolerance)
Design
Property
At 19.2 V DC
At 54 V DC
At 24 to 54 V DC
At 24 V DC
At 54 V DC
 
Basic device
PoE consumers
At 24 to 54 V DC
Quantity
Design
Permitted voltage range
Load capability
With operation with max. PoE load up
to 2000 m above sea level
During storage
During transportation
During operation at 25 ℃
Compact
Technical specifications
8
RJ45 jack
Half/full duplex, MDI‑X pinning; PoE
10 / 100 Mbps
24 to 54 V DC
19.2 to 55 V DC safety extra-low voltage (SELV)
Terminal block, 4 terminals
Implemented redundantly
Max. 7.5 A
Max. 2.5 A
Max. 144 W
Max. 12 W
Max. 10 W
CAT II
2.5 A / 125 V
15 A / 125 V
120 W
Observe the permissible ambient temperature
for operation.
1
Terminal block, 2 terminals
24 VDC
Max. 100 mA
During operation in horizontal installation po‐
sition:
-40 °C to +60 °C
During operation in a different installation po‐
sition:
-40 °C to +50 °C
-40 °C to +85 °C
-40 °C to +85 °C
≤ 95% without condensation
51