A4 TARGET MESSAGES

A4 Target messages
4–32
Courtesy of NationalSwitchgear.com
Target messages are automatically displayed for any active condition on the relay such as
pickups, trips, alarms, or asserted input. The target messages shown in the table below
are displayed as necessary.
The relay displays the most recent event first, and after 5 seconds starts rolling up the
other target messages, until the Reset command is initiated. If the Reset command is not
performed, but any of the other faceplate pushbuttons is pressed, the display will not show
the target messages, unless the user navigates to
where they can be reviewed.
The target messages can be reviewed by pressing Up and Down message pushbuttons
from the relay keypad.
The following table from the 345 Communication Guide shows the list of Target Messages
Code
FC134A
0
7
8
14
15
16
17
18
19
21
0x8040
0x8480
0x84C0
0x8500
0x8540
0x8580
0x85C0
0x8600
0x8640
0x8680
0x89C0
0x8D00
0x8D40
0x8D80
0x8F40
0x9000
0x9040
0x9080
0x90C0
0x9100
0x9140
ACTUAL VALUES > A4 TARGET MESSAGES
Type
Definition
unsigned 16 bits
Active Targets
No Active Targets
Clock Not Set
IRIG-B Failure
Comm. Alert 1
Comm. Alert 2
Comm. Alert 3
Ethernet Link Fail
High ENET Traffic
Ambient Temp. >80C
BKR2 Status Unkwn
Therm O/L Trip
Relay Not Config
LE 1 Trip
LE 2 Trip
LE 3 Trip
LE 4 Trip
LE 5 Trip
LE 6 Trip
LE 7 Trip
LE 8 Trip
Self Test Trip
Rly #1 Trip OP
Rly #2 Trip OP
BKR Failure
Breaker 2 Failure
Ph IOC1 Trip
Ntrl IOC1 Trip
Gnd IOC1 Trip
Ph TOC1 Trip
Ntrl TOC1 Trip
Gnd TOC1 Trip