S2 SYSTEM SETUP
Transformer
Type
2W External
Correction
Y/y180°
Y/d150°
Y/d330°
D/d60°
D/d180°
6–56
Courtesy of NationalSwitchgear.com
TRANSFORMER TYPES
A complete table of two-winding transformer types is shown below.
Table 1: Transformer types
Wdg. Connection
Voltage
Phase
Phasors
Shift
1
WYE (gnd 1/2)
2
WYE (gnd 2/3)
1
WYE (gnd 1/2)
180° lag
2
WYE (gnd 2/3)
180° lag
1
WYE (gnd 1/2)
150° lag
2
DELTA (gnd 2/
3) 150° lag
1
WYE (gnd 1/2)
330° lag
2
DELTA (gnd 2/
3) 330° lag
1
DELTA (gnd 1/
60° lag
2)
2
DELTA (gnd 2/
3) 60° lag
1
DELTA (gnd 1/
180° lag
2)
2
DELTA (gnd 2/
3) 180° lag
Transformer
Wdg. Connection
Type
)
comp
Y/y0°
1
WYE (gnd 1/2)
2
WYE (gnd 2/3)
Y/d30°
1
WYE (gnd 1/2)
2
DELTA (gnd 2/
3) 30° lag
Y/d210°
1
WYE (gnd 1/2)
2
DELTA (gnd 2/
3) 210° lag
D/d0°
1
DELTA (gnd 1/
2)
2
DELTA (gnd 2/
3) 0°
D/d120°
1
DELTA (gnd 1/
2)
2
DELTA (gnd 2/
3) 120° lag
D/d240°
1
DELTA (gnd 1/
2)
2
DELTA (gnd 2/
3) 240° lag
345 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: SETPOINTS
Voltage
Phase
Phasors
Shift
)
comp
30° lag
210° lag
120° lag
240° lag