Keyboard Functions - Cooper Kyle Form 4C Programming Manual

Reclosers microprocessor-based recloser control
Hide thumbs Also See for Kyle Form 4C:
Table of Contents

Advertisement

SAFETY
FOR LIFE
Prior to interrogation and programming, the operator should be familiar with the control's keyboard. Figure 2 shows
each key and its description of operation.
MINIMUM
TCC1
TRIP
1
2
Interrogates or
Interrogates or
programs
programs 1st
minimum trip
TCC (Phase
(Phase and
and Ground)
Ground)
"2" numeric
"1" numeric
value
value
OPER
OPER
1ST TCC
TO L.O.
4
5
Interrogates or
Interrogates or
programs
programs
number of trip
number of
operations on
operations to
1st TCC (Phase
lockout (Phase
and Ground)
and Ground)
"4" numeric
"5" numeric
value
value
RECLOSE
RECLOSE
1
2
7
8
Interrogates or
Interrogates or
programs
programs
reclosing time
reclosing time
after 1st trip
after 2nd trip
operation
operation
"7" numeric
"8" numeric
value
value
PHASE
DISPLAY
TEST
GROUND
0
Toggles
Checks LCD
between Phase
operation by
and Ground
displaying all
Display
numeric
segments and
messages
"0" numeric
value
Figure 2.

Keyboard Functions.

KEYBOARD FUNCTIONS
TCC2
3
Interrogates or
programs 2nd
TCC (Phase
and Ground)
"3" numeric
value
RESET
TIME
6
Interrogates or
programs reset
after successful
reclose time
delay
"6" numeric
value
RECLOSE
3
9
Interrogates or
programs
reclosing time
after 3rd trip
operation
"9" numeric
value
SCROLL
Permits display
of the
programmed
values of most
common control
operating
features
TARGETS
CURRENT
METERING
TARGET
COUNTERS
Displays fault target
Displays Phase
information
and Ground load
current and
Displays cumulative
demand metering
total of fault current
readings
trip phase and
ground. (Used with
SELECT LOWER
FUNCTION key)
OPER.
COUNTER
CODE
SEQUENCE
POSITION
Displays total
Provides direct entry
number of control
of access codes
trip operations
Displays control
operating sequence
position. (Used with
SELECT LOWER
FUNCTION key)
SELECT
ACCESSORY
ACCESSORY
SCROLL
Displays status of
Displays individual
individual control
parameters of
features with
programmable
programmable
control features and
values
accessories
SELECT
ESCAPE
LOWER
FUNCTION
Provides access to
Escape key ignores
Target Counters and
recent keystroke and
Sequence Position
returns to ready
(rdY) prompt
S280-77-4
DISPLAY
ON
OFF
Turns keyboard
and display ON
and OFF
CLEAR
Clears pending
keyboard entries;
resets targets,
counters and
demand drag hand
CHANGE
Initiates change to
programmed
parameter
ENTER
Enters changed
parameter into
program
5

Advertisement

Table of Contents
loading