Changing Control Settings Using Access Codes

Use the following procedure to interrogate or change any control settings of parameters without dedicated keys. Refer
to Table 1 or to the control information label located inside the cabinet door to locate the desired parameter and appro-
priate access code. Enter the desired access code at Step 8.
Change Alternate Phase Minimum Trip Value
(Steps 2 through 6 are required to enter security code. If already in security, omit steps 2 through 6.)
Alternate phase minimum trip is changed from 120 A to 240 A.
Alternate ground minimum trip is changed from 60 A to 120 A.
Step
No.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10
Touch Key
DISPLAY
ON
OFF
CODE
RECLOSE
RECLOSE
3
3
9
9
ENTER
ENTER SECURITY CODE
ENTER
CODE
MINIMUM
MINIMUM
TRIP
TRIP
1
1
ENTER
Display
Access
Message
Code
EXAMINE PHASE
SCROLL CODE
CHANGE GROUND
CODE
EXAMINE PHASE
SCROLL
CODE
CHANGE GROUND
CODE
SCROLL
CODE
CODE
EXAMINE PHASE
SCROLL CODE
CHANGE GROUND
CODE
CODE
EXAMINE PHASE
SCROLL CODE
CHANGE GROUND
CODE
EXAMINE PHASE
SCROLL
CODE
CHANGE GROUND
CODE
EXAMINE PHASE
SCROLL
CODE
CHANGE GROUND
CODE
EXAMINE PHASE
SCROLL CODE
CHANGE GROUND
CODE
Complex
Parameter
TCC
Value
VALUE
VALUE
VALUE
VALUE
As the security code is
entered, the dashes disappear.
The security code will not appear
in the display.
VALUE
VALUE
VALUE
VALUE
VALUE