CIRCUTOR S�A�U� reserves the right to make modifications to the device or the unit specifications set out in this instruction manual without prior notice. CIRCUTOR S�A�U� on its web site, supplies its customers with the latest versions of the device specifi- cations and the most updated manuals.
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 REVISION LOG Table 1: Revision log� Date Revision Description 11/21 M329B01-03-21A Initial release SYMBOLS Table 2: Symbols� Symbol Description In accordance with the relevant European directive. Device covered by European Directive 2012/19/EC. At the end of its useful life, do not leave the device in a household refuse bin.
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 1.- VERIFICATION UPON RECEPTION Upon receipt of the device, check the following points: a) The device meets the specifications described in your order. b) The device has not suffered any damage during transport. c) Perform an external visual inspection of the device prior to switching it on.
Page 7
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 specifies all the device models. Table 3 Table 3:List of models� Current measurement Communications Model LoRa ISM Band) No of Shunt Hall effect RS-485 channels 868 MHz 915 MHz STM-S12-485 STM-S12-F868 ...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 3.- INSTALLATION OF THE DEVICE 3�1�- PRELIMINARY RECOMMENDATIONS In order to use the device safely, personnel operating it must follow the safety meas- ures that comply with the standards of the country where it is to be installed; operators must wear the required personal protective equipment and they must heed the various warnings indicated in this instruction manual.
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 3�2�- INSTALLATION The STM is a device that has specifically been designed to be installed inside an electric cabinet or enclosed, with double insulation, fastened to a DIN rail. Only the measurement circuit can be removed from the enclosure.
LED ED/DI 2 LED ED/DI 3 LED ED/DI 1 Figure 1: STM-S12 and STM-S24 terminals� Table 4:List of terminals: STM-S12 and STM-S24� Device terminals 1: 0, Power supply 26: Current output, channels 8 ... 5 27: CH4, Current input channel 4...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 4.- OPERATION 4�1�- LEDs LED Estado/State LED ED/DI 2 LED ED/DI 3 LED ED/DI 1 Figure 10: LEDs� Table 8: LEDs� LEDs Description On: Indicates that the device is powered and without errors. State Flashing slow: Indicates that the current is running in reverse through one of the channels.
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 4�3�- RTD TEMPERATURE PROBE INPUT The devices have an input for connecting a RTD temperature probe; specifically, a Pt100 probe can be connected (Terminals 47 ... 49 in Terminals 19 ... 21 in Terminals 23 ... 25 in...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 5.- RS-485 COMMUNICATIONS (STM-S12-RS485 AND STM-S24-RS485 MODELS) The SMT-S12-RS485 and SMT-S24-RS485 have an RS-485 communications port, with communica- tions protocols: MODBUS RTU ®. 5�1�- CONNECTIONS The RS-485 cable must be wired using twisted pair cable with mesh shield (minimum 3 wires), with a maximum distance of 1200 meters between the SMT-Sxx-485 and the master unit.
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 5�2�- MODBUS PROTOCOL Within the Modbus protocol, the SMT-Sxx-485 uses the RTU (Remote Terminal Unit) mode. The Modbus functions implemented in the device are as follows: Function 0x02: Reads the status of an input Function 0x03 and 0x04: Reading integer registers.
Page 23
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 Table 11 (Continued): Modbus Memory Map: Instant current measurement of channels� Variable Address Valid data range Units Instantaneous current channel 7 100A 0 ... 10000 A x100 Instantaneous current channel 8 100B 0 ... 10000...
Page 24
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 Table 12 (Continued): Modbus Memory Map: Instantaneous power measurement of channels� Variable Address Valid data range Units Instantaneous power channel 23 1272 0 ... 150 Instantaneous power channel 24 1273 0 ... 150 Table 13: Modbus Memory Map: Average power measurement�...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 5�3�2�- MEMORY MAP IN BLOCKS To simplify readout of a dataset in a single instruction, a set of consecutive memory positions has been established, which we will call blocks. 2 blocks have been used: Block 1: comprising Digital Input status variables, negative current and current deviation Alarms.
Page 26
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 Table 15 (Continued): Modbus Memory Map: Block 1 Variable Address Valid data range Without use 05F8 Without use 05F9 Without use 05FA Without use 05FB Without use 05FC Without use 05FD Without use 05FE Without use...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 For the variables of Block 2, Function 0x04 is implemented. Table 16: Modbus Memory Map: Block 2� Block 2 Variable Address Valid data range Units Temperature of the STM device 3520 -200... 1000 ºC ºC x 10...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 6.- WIRELESS COMMUNICATIONS (STM-xxx-Fxxx Models) The STM-xxx-Fxxx model has a built-in gateway for converting data between the RS-485 physical environment and the LoRa long-range wireless network. 6�1�- USAGE ENVIRONMENT AND HEALTH Like other radio devices, wireless communications emit electromagnetic RF energy.
Page 30
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 RS-485 LoRa™ LoRa™ LoRa™ LoRa™ Bus 1 Bus 2 Bus 3 Figure 12: Example of LoRa connection� Up to 32 end devices can be connected to each communications bus. Communications between the LoRa master and slave devices are completely transparent, allowing for a simple installation where you only need to check the transmission time between messages and the timeout time from the application master.
Page 31
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 Table 20 (Continued): Transmission-Reception Modes� Mode Speed Description 976.56 bps 1171.88 bps 1953.13 bps 2148.44 bps 3515.63 bps 7031.25 bps 12500 bps 21875 bps Minimum distance: , Maximum speed: Note: Check the guide "Guide to implementing LoRa-Modbus communications in the STM"...
Min� voltage measurement (Vstart) - 25 V Max� consumption of the voltage input 0.625 mA Installation category CAT II 1500 V Current measurement circuit (STM-S12 and STM-S24 Models) STM-S12 STM-S24 Channels Current measurement margin 0.1 ... 45 A 0.1 ... 30 A Min�...
Page 33
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 Wireless communications Band 2.4 GHz RS-485 communications (STM-S12-485 and STM-S24-485 Models) Protocol Modbus RTU Baud rate 9600 - 19200 - 38400 - 57600 - 115200 Data bits Parity without Stop bits LoRa communications (STM-Sxx-Fxxx, STM-H6, STM-H10 and STM-H20 Models)
Page 34
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 (Continuation) Mechanical features (STM-H6 Model) Enclosure Self-extinguishing V0 plastic Attachment DIN rail Mechanical features (STM-H10 Model) Terminals 1...10 < 8.4 mm 11, 12 0.75 ... 16 mm 18 mm 13 ... 21, 23 ... 25 0.2 ...
STM-S12, STM-S24, STM-H6, STM-H10, STM-H20 8.- MAINTENANCE AND TECHNICAL SERVICE In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR S�A�U� Technical Support Service. Technical Assistance Service Vial Sant Jordi, s/n, 08232 - Viladecavalls (Barcelona) Tel: 902 449 459 (Spain) / +34 937 452 919 (outside of Spain) email: sat@circutor.com...