CIRCUTOR S�A�U� reserves the right to make modifications to the device or the unit specifications set out in this instruction manual without prior notice. CIRCUTOR S�A�U� on its web site, supplies its customers with the latest versions of the device specifi- cations and the most updated manuals.
- MYeBOX markers in 9 colours. - Wireless connector for the transistor's digital inputs/outputs ( Kit A_MYeBOX 1500 and Kit A_MYeBOX-1500-4G). Kit MYeBOX 150, Kit MYeBOX 1500 and Kit MYeBOX-1500-4G: - An installation guide. - 1 battery. - 1 AC power supply adaptor.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 2.- PRODUCT DESCRIPTION MYeBOX is a portable analyzer that measures, calculates and displays the main parameters of any electrical installation (single-phase, two-phase with and without neutral, balanced or unbalanced three-phase and through an ARON connection) MYeBOX can be fully configured remotely and can display electrical parameters on a smartphone or tablet using a mobile application connected to a Wi-Fi network.
Page 9
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G - 4G communications (MYeBOX-1500-4G). - Wi-Fi communications. - 1 μUSB connector to connect and download data to a PC. The MYeBOX mobile application lets you fully program the MYeBOX remotely, configure the measure- ment, display the most important parameters and send logs to MYeBOX Cloud.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 3.- DEVICE INSTALLATION 3�1�- PRELIMINARY RECOMMENDATIONS In order to use the device safely, it is essential that the individuals who handle it follow the safety measures set out in the standards of the country where it is being used, use...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 3�2�- BATTERY INSTALLATION Do not disassemble or modify the battery. The warranty does not cover any battery not delivered by Circutor or batteries that have been disassembled or modified. There is a risk of explosion if installed incorrectly.
Page 12
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Figure 2:Removal of the battery cover� Connect the battery, Figure 3 Figure 3:Connect the battery� Insert the connection cable inside the battery cover, Figure 4 Figure 4:Insert the connection cable inside the battery cover�...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Figure 5: Inserting the battery� Disconnect the battery if the device is going to be idle for more than 3 months. If the device has been without power for more than 4 weeks, it is recommended to load a few hours before use.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G To install the strap on the device, follow these steps: Figure 7: Installation of the fastening strap: Steps 1 and 2� Figure 8: Installation of the fastening strap: Steps 3 and 4� 3�4�- MYeBOX 480V ~ PSU ADAPTER : POWER SUPPLY ADAPTER Note: The MYeBOX 480V ~ power supply adapter is an accessory sold separately.
Page 15
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 3 (Continuation): MYeBOX 480V~ PSU ADAPTER Technical features� Output Environmental features Operating temperature 0ºC ... +40ºC Storage temperature -20ºC ... +70ºC Relative Humidity (non-condensing) 5 ... 95 % Maximum altitude 2000 m Protection degree...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 3�5�- VOLTAGE CABLES To measure voltage, you must use 600 V CAT III double-insulated connection cables. The Kit B_MYeBOX 150, Kit B_MYeBOX 1500 and Kit B_MYeBOX-1500-4G kits come with the neces- sary cables: - UL 600 V CAT III double-insulated voltage cables, or higher.
3�7�- DEVICE TERMINALS 3�7�1�- MYeBOX 150 Table 7:List of terminals on the lower face of the MYeBOX 150� Device terminals on the lower face of the MYeBOX 150 1: U1, Voltage input L1 5: I1, Current input L1...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Figure 11:MYeBOX 150 terminals, upper face� 3�7�2�- MYeBOX 1500 and MYeBOX-1500-4G Table 9:List of terminals on the lower face of the MYeBOX 1500 / MYeBOX-1500-4G� Device terminals on the lower face of the MYeBOX 1500 / MYeBOX-1500-4G...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 3�8�2�- THREE-PHASE NETWORK MEASURING WITH A 4-WIRE CONNECTION (MYeBOX 1500, MYe- BOX-1500-4G)� Type of installation (Select circuit) : 3 Phases + Neutral. ALIMENTACIÓN AUXILIAR POWER SUPPLY U2 U3 URef CARGA / LOAD Figure 15: Three-phase measuring with a 4-wire connection (MYeBOX 1500, MYeBOX-1500-4G)�...
Page 22
ALIMENTACIÓN AUXILIAR POWER SUPPLY U2 U3 CARGA / LOAD Figure 16: Three-phase measuring with a 3-wire connection (MYeBOX 150, MYeBOX 1500, MYeBOX-1500-4G)� Note: See section “ 3.8.10.- DETAIL OF THE CURRENT MEASUREMENT CONNECTION.” See “5.2.- DISPLAY MENU: DEVICE PROFILE” Instruction Manual...
ALIMENTACIÓN AUXILIAR POWER SUPPLY U2 U3 CARGA / LOAD Figure 17: Three-phase measuring with a 3-wire connection and an ARON connection (MYeBOX 150, MYeBOX 1500, MYeBOX- 1500-4G)� Note: See section “ 3.8.10.- DETAIL OF THE CURRENT MEASUREMENT CONNECTION.” See “5.2.- DISPLAY MENU: DEVICE PROFILE”...
ALIMENTACIÓN AUXILIAR POWER SUPPLY CARGA / LOAD Figure 20: Single-phase measurement, phase to neutral, with a 2-wire connection (MYeBOX 150, MYeBOX 1500, MYeBOX-1500-4G)� Note: See section “ 3.8.10.- DETAIL OF THE CURRENT MEASUREMENT CONNECTION.” See “5.2.- DISPLAY MENU: DEVICE PROFILE”...
: 1 Phase + Neutral. (10) ALIMENTACIÓN AUXILIAR POWER SUPPLY CARGA / LOAD Figure 21: Single-phase measurement, phase to neutral, with a 2-wire connection (MYeBOX 150)� Note: See section “ 3.8.10.- DETAIL OF THE CURRENT MEASUREMENT CONNECTION.” See “5.2.- DISPLAY MENU: DEVICE PROFILE” (10)
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 3�9�- REGISTERING AND UPDATING THE DEVICE Before using the device for the first time, it is necessary to: 1�- Register the MYeBOX on the web page www�myebox�es 2�- Register the device on a network with Internet connection.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 4.- OPERATION 4�1�- OPERATING PRINCIPLE The MYeBOX is a four-quadrant portable power analyzer (consumption and generation). 90º kW + kW - kvarL PF - PF + kvarC kvar + Cos φ - kvar - Cos φ...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 4�2�- MEASUREMENT PARAMETERS The device measures and logs different types of parameters: Electrical parameters, Quality parameters (EVQ) such as overvoltages, gaps and outages, in accordance with EN50160. Wave shapes of the different channels.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 11 (Continued): MYeBOX measurement parameters� Parameter Units Tariff: T1-T2 Wave shapes Phasor representation No. of hours of active tariff hours (12) Cost COST (12) Emissions...
Page 34
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G this example it is 10% of the rated voltage plus the time the signal takes to rise above the configured value, including a hysteresis of 2%. Transients Transients are detected by checking that the difference between one sample and the next does not exceed the maximum nominal slope value multiplied by the distortion level coefficient selected by the user (“...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Table 13: Key functions: Display menus� Press Go to the previous display screen. Go to the next display screen. Access the display menu. Access the setup menu from the Setup menu Go to the next display menu.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 4�5�- LED INDICATORS 4�5�1�- MYeBOX 150� The MYeBOX 150 model has 14 indicator LEDs, as shown in Figure 34 Table 15 Memory Battery DATE TIME 25/06/2015 15:07:50 Figure 34:MYeBOX 150 indicator LEDs� Table 15: LED description, MYeBOX 150�...
Page 38
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Table 15 (Continued): LED description, MYeBOX 150� Description Blinking light (0�5 s) Battery Red: Battery not charging, charge < 5%. Power off No access to the MicroSD memory; the USB cable does not have to be connected.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G The name of the log where all the measurements will be saved is configured in the Device profile setup menu ( “6.2.2.- MEASUREMENT NAME” The device adds the configured name to the recording date so that the same name can be used for more than one log.
Page 43
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 18:�EVA file description� EVENT DESCRIPTION BAT_ON Battery powered device. BAT_OFF Battery level that causes the device to switch off CLEAR_ENERGY Energy loss (boot) SETUP_LOST Setup loss (defect) SETUP_CHANGED Change of a configuration parameter SETUP_TRANS_RATIO_CHANGED Change of transformation ratio configurations.
Page 44
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 4�8�2�2� �EVQ file All quality events are stored in the �EVQ file. The following data are stored from each one of the events: Table 19: Quality event� DATA DESCRIPTION Event Type Overvoltage, Gap, Interruption or Transient...
Page 45
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 20 (Continued) : List of variables that can be included in the STD file Phases Total Record Variables Unit L1-L2-L3 Period (16) THD % current (average, maximum, minimum) % THD A 5 min ...
Page 46
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Some of the variables in the STD file require an explanation: Instant Flicker and PST Flicker: The device will record the instant Flicker and the value obtained during the recording period (Flicker PST).
Page 47
1 + =2 MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G rent. The purpose of the crest factor is to give an idea of the wave peak and it is used primarily for current waves. � � = ...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 5.- DISPLAY The parameters shown by the device on the screen are organised into different display menus, as shown in Figure 38 MEASURE Measures DEVICE PROFILE Device profile QUALITY Quality Communications COMMUNICATIONS Date...
Page 49
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Once the device has finished booting up, the display shows the first screen of the Measure display menu, as shown in Figure 39 230.0 230.0 230.0 Figure 39:Phase-neutral voltage screen, measure menu� If the device detects a system error, the error screen appears as shown in...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 5�1�- DISPLAY MENU: MEASURE shows the main screen of the Measure display menu, showing all the device’s measuring Figure 42 parameters. MEASURE Figure 42:Measure display menu, main screen� Press the key to enter the display menu.
Page 51
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 22 (Continued): Measure display menu� Measure display menu COS1 COS2 COS3 -0.80 -1.00 -0.50 Cos φ, of each of the phases. (17) COS l l l PF l l l 1.00 -0.95 Cos φ III and Power Factor III...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 5�2�- DISPLAY MENU: DEVICE PROFILE shows the main screen of the Device Profile display menu, showing all the device's profile. Figure 43 DEVICE PROFILE Figure 43:Device Profile display menu, main screen� Press the key to enter the display menu.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 5�3�- DISPLAY MENU: QUALITY shows the main screen of the Quality display menu, showing all the device's quality Figure 44 parameters. QUALITY Figure 44:Quality display menu, main screen� Press the key to enter the display menu.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 5�4�- DISPLAY MENU: COMMUNICATIONS shows the main screen of the Communications display menu, showing full information about Figure 45 the device's active communications. COMMUNICATIONS Figure 45:Communications display menu, main screen� Press the key to enter the display menu.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 25 (Continued): Communications display menu� Communications display menu Note Note : Screen visible on the MYeBOX 1500 : Screen visible on the MYeBOX-1500-4G model model 3G SIGNAL MODEM SIGNAL 86 % 86 %...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 5�6�- DISPLAY MENU: INFORMATION shows the main screen of the Information display menu, showing full information about the Figure 47 device. INFORMATION Figure 47:Information display menu, main screen� Press the key to enter the display menu.
Page 57
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G The error code displayed by the device is the hexadecimal value of all the error bits that are active in MyEBOX. shows the description and action of each error bit. Table 28 Table 28: Error code�...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 5�7�- DISPLAY MENU: ENERGY RATIOS , shows the main screen of the Energy Ratios menu, displaying all of the device’s energy Figure 48 ratios. ENERGY RATIOS Figure 48: Energy Ratios display menu, main screen�...
Page 59
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Table 30 (Continued) : Energy Ratios display menu Menú de visualización Measure hourT2- costT2- 7.85165 No� of hours of the active Tariff 2 (Energy Generated) Cost per kWh of Tariff 2 (Energy Generated) KgCO2T2- 50.70000...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G If from any setup menu screen no key is pressed for 5 minutes, the device quits the setup menu and returns to the Phase-Neutral Voltages screen of the Measure display menu. Note: Setup menu changes must be made while data logging is off.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�1�2�- PRIMARY VOLTAGE This screen is used to configure the primary winding of the voltage transformer. PRIMARY VOLTAGE 000001 Press the key to enter edit mode. Use the keys to write or change the value of the blinking digit.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�1�4�- PHASE CLAMP SCALE This screen is used to select the scale of the clamps selected for measuring the phase. Note: If the clamp only has one scale, this parameter cannot be edited. PHASE CLAMP SCALE Press the key to enter edit mode.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�1�6�- NEUTRAL CLAMP SCALE This screen is used to select the scale of the clamp selected for measuring the neutral. Note: If the clamp only has one scale, this parameter cannot be edited.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�1�8�- CLAMP SCALE FOR MEASURING THE LEAKAGE CURRENT, ILeak Note: Configuration parameter available for the MYeBOX 1500 / MYeBOX-1500-4G model. This screen is used to select the scale of the clamp selected for measuring the leakage current.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�1�10�- FREQUENCY This screen is used to select the operating frequency. FREQ HZ 50.00 Press the key to enter edit mode. Use the keys to browse the different options: , 50 Hz. 50.00 , 60 Hz, 60.00...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�2�- SETUP MENU: DEVICE PROFILE SETUP shows the main screen of the Device Profile setup menu where the device's profile can be Figure 51 configured. DEVICE PROFILE SETUP Figure 51:Device Profile setup menu, main screen�...
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�2�3�- TYPE OF INSTALLATION This screen is used to configure the installation type. SELECT CIRCUIT 3 PHASES + NEUTRAL Press the key to enter edit mode. Use the keys to browse the different options:...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�3�- SETUP MENU: QUALITY SETUP shows the main screen of the Quality setup menu, where the device's quality parameters Figure 52 are configured. QUALITY SETUP Figure 52:Quality setup menu, main screen� Press the key to enter the setup menu.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Note: Set the value to 0 to stop recording gaps. Press the key to confirm. Use the keys to toggle between the menu's setup screens. 6�3�3�- OUTAGE, INTERRUPTION This screen is used to configure the threshold value for logging outages, as a percentage of the rated voltage value.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�3�5�- SAVE Press the key to save the changes and to go to the main screen of the Quality setup menu. SAVE Use the keys to toggle between the menu’s setup screens. 6�3�6�- EXIT key to exit to the main screen of the Quality setup menu without saving modified values.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G Press the key to confirm the option selected. Use the keys to toggle between the menu's setup screens. 6�4�2�- SSID Note: This configuration parameter cannot be edited if was selected for the “...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�4�4�- PASSWORD Note: This configuration parameter cannot be edited if was selected for the “ 6.4.1.- Wi-Fi ACCESS POINT ” parameter or was selected for the “ ” parameter 6.4.3.- WPS CONFIGURATION MYeBOX_083115331025 This screen is used to configure the Wi-Fi network password.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�4�6�- APN, ACCESS POINT NAME Note: Configuration parameter available for the MYeBOX 1500 / MYeBOX-1500-4G model. Note: This configuration parameter cannot be edited if was selected for the “ 6.4.5.- ENABLING DISABLE ” parameter.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 6�4�8�- APN, PASSWORD Note: Configuration parameter available for the MYeBOX 1500 / MYeBOX-1500-4G model. Note: This configuration parameter cannot be edited if was selected for the “6.4.5.- ENABLING DISABLE ” parameter. 3G / 4G COMMUNICATIONS This screen is used to configure the APN password for 3G (MYeBOX 1500) or 4G (MYeBOX-1500-4G communications.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�4�10�- SAVE Press the key to save the changes and to go to the main screen of the Communications setup menu. SAVE Use the keys to toggle between the menu’s setup screens. 6�4�11�- EXIT...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G Press the key to confirm the option selected. Use the keys to toggle between the menu’s setup screens. 6�5�2�- SAVE Press the key to begin deletion of the database. SAVE While the deletion is being performed, the following screen will be shown: FORMATTING ..
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 6�6�- SETUP MENU: RESET FACTORY SETUP shows the main screen of the Reset Factory setup menu where the default values of the Figure 55 unit can be loaded. RESET FACTORY SETUP Figure 55: Reset facvtory setup menu, main screen�...
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 7.- WIRELESS COMMUNICATIONS The device has the following wireless communications: MYeBOX 150 model: Wi-Fi communications. MYeBOX 1500 / MYeBOX-1500-4G model: Wi-Fi communications. 3G (MYeBOX 1500) or 4G (MYeBOX-1500-4G) communications. 7�1�- USAGE ENVIRONMENT AND HEALTH Wireless communications emit radio frequency electromagnetic energy, like other radio devices.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 7�2�- LOCATION OF THE ANTENNAS The device has two antennas for Wi-Fi, 3G and 4G connections. 3G (MYeBOX 1500) 4G (MYeBOX-1500-4G) Wi-Fi Figure 56:Location of the wireless antennas� The antennas have a standard connector so they can be exchanged for larger ones if the application requires greater coverage.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 7�4�- 3G (MYeBOX 1500 model) / 4G (MYeBOX-1500-4G model) COMMUNICATIONS The MYeBOX 1500 / MYeBOX-1500-4G model has 3G / 4G communications, so the device can be con- nected and exchange data with other mobile devices without a Wi-Fi connection.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 8.- MOBILE APPLICATION MYeBOX The device has the MYeBOX mobile application, which allows users to wirelessly connect to the devices using Wi-Fi, 3G (MYeBOX 1500 model) or 4G (MYeBOX -1500-4G model) communications and: Fully configure the device.
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G 10�2�- UPDATING THROUGH THE MOBILE APPLICATION With MYeBOX switched on: 1�- Open the MYeBOX mobile application. 2�- If there is a new version of the device, the application indicates this in the Setup / Firmware menu.
MYeBOX 150 - MYeBOX 1500 - MYeBOX-1500-4G 11.- TECHNICAL FEATURES Power supply (AC power supply adaptor) Input Rated voltage 100 ... 240 V ~ Frequency 47 ... 63 Hz MYeBOX 1500 MYeBOX 150 MYeBOX-1500-4G Consumption 22... 28 VA 25... 31 VA...
Page 85
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G (Continued) Accuracy of measurements (20) Reactive energy measurement Class 1 (IEC 62053-23) Frequency measurement Clase A ( 42.5 ... 69 Hz) (IEC 61000-4-30) Power factor measurement Class 0.5 (IEC 61557-12) Voltage THD measurement Class I (IEC 61000-4-7)
Page 87
MYeBOX 150 - MYeBOX 1500- MYeBOX-1500-4G (Continued) Environmental features Maximum altitude 2,000 m Protection degree IP30 Mechanical features Dimensions Figure 58 (mm) MYeBOX 1500 MYeBOX 150 MYeBOX-1500-4G Weight 950 g 975 g Enclosure V0 self-extinguishing plastic Standards Electrical equipment for measurement, control and laboratory use - EMC re-...
The device does not need any maintenance. Only clean the screen with soapy water and dry with a soft dry cloth. In the case of any query in relation to device operation or malfunction, please contact the CIRCUTOR S�A�U� Technical Support Service.
Need help?
Do you have a question about the MYeBOX 150 and is the answer not in the manual?
Questions and answers