NetSure™ -48 VDC
Battery Rack System
Installation and User Manual
Specification Number: 588820400100, 588820400150, 588820400200
Model Number: 48BA800-23

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NetSure 48 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Vertiv NetSure 48 Series

  • Page 1 NetSure™ -48 VDC Battery Rack System Installation and User Manual Specification Number: 588820400100, 588820400150, 588820400200 Model Number: 48BA800-23...
  • Page 2 The information contained in this document is subject to change without notice and may not be suitable for all applications. While every precaution has been taken to ensure the accuracy and completeness of this document, Vertiv assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions.
  • Page 3: Table Of Contents

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual TABLE OF CONTENTS Admonishments Used in this Document ..........................iv Important Safety Instructions ..............................v Safety Admonishments Definitions ............................................v Safety and Regulatory Statements ............................................v Déclarations de Sécurité et de Réglementation ......................................v 1 Customer Documentation Package ..........................1...
  • Page 4: Admonishments Used In This Document

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Admonishments Used in this Document will likely DANGER! Warns of a hazard the reader be exposed to that will result in death or serious injury if not avoided. (ANSI, OSHA)
  • Page 5: Important Safety Instructions

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Important Safety Instructions Safety Admonishments Definitions Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv. Safety and Regulatory Statements Refer to Section 4154 (provided with your customer documentation) for Safety and Regulatory Statements.
  • Page 6 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual This page intentionally left blank. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 7: Customer Documentation Package

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 1 Customer Documentation Package This document (IM588820400100) provides Installation and User Instructions for Vertiv™ NetSure™ -48 VDC Battery Rack System Model 48BA800-23; Spec. No. 588820400100, 588820400150, and 588820400200. The complete Customer Documentation Package consists of…...
  • Page 8: Installing The System

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 4 Installing the System 4.1 General Requirements • This product is intended only for installation in a restricted access location on or above a non-combustible surface. • This product must be located in a controlled environment with access to Crafts persons only.
  • Page 9: Securing The System's Box Framework(S) To The Floor

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 4.2 Securing the System’s Box Framework(s) to the Floor Secure the box framework to the floor per site requirements. Refer to “General Requirements” on page 2. Refer to Figure 4.1 for floor mounting hole dimensions.
  • Page 10 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Figure 4.2 Optional Battery Rack Isolation Kit Mounting 1/2-inch Flat Washer (inside box framework Battery Rack at mounting locations) Box Framework (4-places) 1/2-inch Bushing (inside box framework at mounting locations)
  • Page 11: Making Electrical Connections

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 5 Making Electrical Connections 5.1 Important Safety Instructions DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document. 5.2 Wiring Considerations All wiring should follow the current edition of the American National Standards Institute (ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code (NEC), and applicable local codes.
  • Page 12: Battery Disconnect Circuit Breakers External Alarm Connections

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 5.5 Battery Disconnect Circuit Breakers External Alarm Connections The battery disconnect circuit breakers are factory wired to an alarm card located at the top of the box framework. The alarm card provides resistive battery and Form-C relay contacts for connection to external alarm circuits.
  • Page 13: Battery Connections To Associated Power System

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 5.6 Battery Connections to Associated Power System Lug-terminated battery leads must extend from the termination busbars located at the top of the battery rack system to the battery busbar and battery return busbar of the associated power system. Refer to the documentation provided with the power system for connections to the power system.
  • Page 14: Installing Batteries

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 6 Installing Batteries 6.1 Important Safety Instructions DANGER! Adhere to the “Important Safety Instructions” presented at the front of this document. DANGER! Batteries are heavy (up to 151 lbs.). Two people are recommended for lifting and placing batteries in lower battery trays (trays below waist height).
  • Page 15 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Note! Ensure the spacers provided on each front cover slide between the batteries. To connect the batteries to the power system, turn ON the battery disconnect circuit breakers (located on the front of the box framework, adjacent to each battery tray).
  • Page 16 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Figure 6.1 Installing Batteries into a Battery Tray (cont’d from previous page) Installing Front Covers 3/8” Ground Washer Mount Covers to Rack 3/8” Flat Washer 3/8” Ground Washer 3/8-16 x 1” Bolt 3/8”...
  • Page 17 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Figure 6.2 Installing Battery Retainer Kit (cont’d on next page) Top Retainer Bracket Front Retainer Bracket Battery Retainer Kit Higher Battery Retention Bracket as Required See Detail A Detail A Torque to 31 in-lbs.
  • Page 18 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Figure 6.2 Installing Battery Retainer Kit (cont’d from next page) Installing Front Brackets 3/8” Ground Washer 3/8” Flat Washer 3/8-16 x 1” Bolt (4 places) Torque to 180 in-lbs 3/8”...
  • Page 19: Initially Starting The System

    Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual 7 Initially Starting the System Procedure Ensure all furnished protective covers are installed. Turn ON the battery disconnect circuit breakers (located on the front of the box framework, adjacent to each battery tray).
  • Page 20 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual This page intentionally left blank. Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 21 Vertiv™ NetSure™ -48 VDC Battery Rack System Installation and User Manual Connect with Vertiv on Social Media https://www.facebook.com/vertivI https://www.instagram.com/vertiv/ https://www.linkedin.com/company/vertiv/ https://www.twitter.com/vertiv/ Proprietary and Confidential © 2022 Vertiv Group Corp.
  • Page 22 Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA © 2022 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp.

This manual is also suitable for:

Netsure 48ba800-23

Table of Contents