7.2.13. Zero current calibration

This option can be used to calibrate the zero reading if the battery monitor reads a non-zero current even when there is no load
and the battery is not being charged.
A zero current calibration is (almost) never needed. Only perform this procedure in case the battery monitor shows a current while
you are absolutely sure that there is no actual current flowing. The only way to be sure is to physically disconnect all wires and
cables connected to the LOAD MINUS side of the shunt. Do this by unscrewing the shunt bolt and removing all cables and wires
from that side of the shunt. The alternative, switching loads or chargers off, is NOT accurate enough as this does not eliminate
small standby currents.
Ensure that there really is no current flowing into or out of the battery (disconnect the cable between the load and the shunt), then
press CALIBRATE in the VictronConnect app.

7.3. Alarm settings

The SmartShunt is not equipped with a buzzer or an alarm relay like the BMV series is. The generated alarms are only visible on
the VictronConnect app while connected to the SmartShunt or are used to send an alarm signal to a GX device.
Alarms are disabled by default. To enable do the following:
• In the VictronConnect app, enable the alarm by sliding the slider button to the right.

7.3.1. Low SoC alarm settings

When enabled, the alarm will activate when the state of charge (SoC) falls below the set value for more than 10 seconds. The
alarm will deactivate when the state of charge rises above the clear value
Setting
Set alarm value
Clear alarm value

7.3.2. Low voltage alarm

When enabled, the alarm will activate when the battery voltage falls below the set value for more than 10 seconds. The alarm will
deactivate when the battery voltage rises above the clear value.
Page 24
Manual - SmartShunt IP65
Performing a zero current calibration.
Default
1%
1%
Range
Steps
0 - 100%
1%
0 - 100%
1%