Scroll compressors, DSH090 to DSH600 | Mechanical connections
Figure 29: DSH240-295-381 mounting
1
2
3
4
5
1
Tightening torque 16Nm
2
Not supplied Φ10mm
3
Tightening torque 50Nm
4
Tightening torque 55Nm
5
5mm (0.2inch) thickness
Tandem requirements DSH482 to DSH1800 mounting (except DSH565)
For parallel mounting, the compressors can be mounted directly on the rails. Rubber grommets and spacers must be
installed below the rails.
These parts are included in accessories.
Figure 31: DSH482 to DSH1800 mounting (except DSH565)
1
2
3
© Danfoss | Climate Solutions | 2022.10
Figure 30: DSH120-161-184 mounting
6
Tightening torque 15Nm
7
4mm (0.16inch) thickness
Supplied with the compressor
Included in manifolding kit
Not supplied
1
HM10 x 30 class 10.9 Tightening torque 50
Nm
2
HM10 x 100 class 10.9 Tightening torque
50Nm
3
Thickness : 5mm (0.2 inch) (6mm (0.24 inch)
for manifold configurations using one or
several DSH600)
Included in tandem/trio kit
Not supplied
AB288965961751en-001402 | 30
6
7
5