Scroll compressors, DSH090 to DSH600 | Mechanical connections
Manifolding requirements DSH180E-210E-240E-280E-322E-368E and DSH260U-281U-301U
mounting
The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be
installed below the rails.
The rigid mounting spacers are included in tandem accessory kits. The rubber grommets are supplied with
compressor.
For more details about parallel mounting feet, please see parallel unit outline drawing.
Figure 27: DSH180E to DSH368E and DSH260U-281U-301U mounting
1
2
3
4
Manifolding requirements DSH195U-210U-230U-251U-274U-289U-304U-324U-345U mounting
The compressors must be mounted with rigid mounting spacers on rails. Rubber grommets and spacers must be
installed below the rails.
The rigid mounting spacers are included in tandem accessory kits. The rubber grommets are supplied with
compressor.
1
2
3
5
4
© Danfoss | Climate Solutions | 2022.10
1
Tightening torque 15Nm
2
Not supplied Φ8x75mm 0.31x2.95inch
3
Tightening torque 15Nm
4
4mm (0.16 inch) thickness
Supplied with the compressor
Included in manifolding kit
Not supplied
1
2
3
4
AB288965961751en-001402 | 28