Hygrostat control

Built in hygrostat
The dehumidifier is controlled by a built-in hygrostat that is set to approx. 60 % RH.
When the hygrostat registers a relative humidity of more than 60 %, the compressor and
the fan(s) automatically switch on and the dehumidifier starts to dehumidify. The hygro-
stat is located next to the evaporator at the base of the compressor housing.
Important
If the air humidity is below 60 %RH, the unit will not start when the power is connected.
Adjustment of the
To set the hygrostat lower than 60 %RH,
hygrostat
turn the control button:
Constant measure
Dantherm recommends that an external hygrostat is installed to ensure a constant
of the humidity
measure of the humidity in the pool area.
Repeatedly adju-
We recommend installing an external hygrostat if you want to change/adjust the setting
stments
of relative humidity very often.
Extra hygrostat is as accessory available.
Connection of ex-
Please follow this procedure to connect an external hygrostat.
ternal hygrostat
The outlet for the external hygrostat is 12 V.
22
Step
1
Uncouple the built-in hygrostat from the terminals 21/22
2
Mount the external hygrostat to the terminals 21/22
3
Lead out the hygrostat cable through the base of the unit
4
Fix the hygrostat to a wall in an appropriate place
Action