Dantherm CDP 35 Service Manual page 24

Hide thumbs Also See for CDP 35:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 17
Mounting and installation instructions,
Condensate outlet
The condensate outlet is located at the base of the dehumidifier. The unit has a drain
spigot intended for connection of a ½'' flexible or fixed water hose. If you choose to
have the outlet through the wall, a matching hole is made in the wall and the drain pipe
is connected to the dehumidifier before it is placed on the wall suspension bar.
It is important that the hose from the dehumidifier to the drainage has a fall of at least
2 % to make sure that the water runs away from the condensate tray.
As an alternative a condensate pump can be fitted at the water outlet to pump the water
to a drain.
The position of the condensate outlet is shown on the drawing – the unit is seen from
above.
Illustration
Position of the drain:
Connection of
Power is connected to the unit in accordance with the nameplate. Please see wiring dia-
power supply
grams on pages 97-99.
Important! All electrical connections must be made in accordance with local power sup-
Water quality
Instructions from the supplier of the water treatment plant must always be respected.
With the addition of
The following guidance values are applicable to swimming pools with the addition of
chemicals
chemicals
Free chlorine content
Combined chlorine content
pH
Total alkalinity
Calcium hardness
Total dissolved solids
Sulphates
24
ply company regulations!
Chemicals
continued
1,0-2,0
Max. 1/3 of free chlorine content
7,2-7,6
80-150
250-450
< 2000
< 360
ppm
Continued overleaf