Devicenet master/slave module
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

Event
Communication
Overview
code
error code
2AnnH
Polling response data length
abnormality
00C08
2BnnH
Polling response divide receive
abnormality
00C09
2CnnH
Polling response divided data
number abnormality
00C10
2DnnH
Polling response divided data
receive abnormality
00C11
3BnnH
Node address duplication
abnormality
00C12
47nnH
Connection type abnormality
61nnH
Number of transmit byte
abnormality
00C13
80nnH
Polling connection timeout
00C14
81nnH
Connection Allocate abnormality
00C15
82nnH
Number of receive byte
abnormality
83nnH
Polling fragmented sequence
abnormality
00C20
20FEH
Data consistency setting
abnormality
00C21
21FEH
Data consistency setting
abnormality
00C22
22FEH
Data consistency setting
abnormality
00C23
23FEH
Data consistency setting
abnormality
Operation
Event code
Overview
24000
I/O communication start request
24001
I/O communication stop request
24002
Master function error reset request
24003
Auto configuration request
24004
Parameter save request to Flash ROM
24005
Slave function error reset request
24008
Own node reset request receive
24009
Other node reset request
2A000
Parameter clearing in flash ROM request
Cause
The polling response data length differs from the data length read from the slave node at
connection establishment.
For divide receive of the polling response, the first divided data has been received twice.
[Example]
• The terminating resistor came off.
For divide receive of the polling response, the number of the received divided data is
different from the expected one.
[Example]
• The terminating resistor came off.
For divide receive of the polling response, the intermediate data or final data has been
received before the first divided data has been received.
[Example]
• The terminating resistor came off.
Two or more same node addresses (MAC ID) are detected among the parameters.
An improper connection type has been specified by the slave node at connection
establishment.
The error cause can be acquired by the communication error information read.
The transmit byte of the slave function is out of range.
The polling connection of the slave function became timeout.
[Example]
• The terminating resistor came off.
• The master node is abnormal.
The connection other than the explicit message or polling.
[Example]
• The connection type of the master node is set to other than the polling.
The number of receive byte of the polling exceeds the maximum number of receive
points.
[Example]
• The number of I/O points setting of the master node exceeds the maximum number of
the RJ71DN91.
An error has occurred in a polling fragmented sequence.
Although the data consistency setting of the master function is enabled, DNTMRD or
M+RJ71DN91_MasterRead is not executed in three sequence scans.
Although the data consistency setting of the master function is enabled, DNTMWR or
M+RJ71DN91_MasterWrite is not executed in three sequence scans.
Although the data consistency setting of the slave function is enabled, DNTSRD or
M+RJ71DN91_SlaveRead is not executed in three sequence scans.
Although the data consistency setting of the slave function is enabled, DNTSWR or
M+RJ71DN91_SlaveWrite is not executed in three sequence scans successively.
Cause
I/O communication start has been instructed by I/O communication request.
I/O communication stop has been instructed by I/O communication request.
Master function error reset request has been.
Auto configuration request has been transmitted.
Parameter saving to flash ROM has been requested.
Slave function error reset request has been transmitted.
A reset request of the own node has been received from other nodes.
A reset has been requested to other nodes.
Parameter clearing in flash ROM has been requested.
4 TROUBLESHOOTING
4.6 List of Error Codes
4
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-rj71dn91

Table of Contents