B. Subnet Mask: When operating in DHCP, the router will assign the subnet mask values.
C. Gateway: Enter the TCP/IP gateway of the network access point (router) being used.
D. HTTP Port: Enter the HTTP port number assigned to the LINQ8PD(CB) module by the network
administrator to allow remote access and monitoring. The default inbound port setting is 80. HTTP is not
encrypted and unsecure. Even though HTTP can be used for remote access, it is recommended primarily
for use with LAN connections.
Secure Network Setup (HTTPS):
In order to setup HTTPS for a Secure Network Connection, a Valid Certificate and Key must be used. Certificates
and Key should be in a ".PEM" format. Self Certifications should only be used for testing
purposes as no actual authentication is being performed. In a Self-Certified mode, the connection will still
state that it is unsecure. How to upload Certificate and Key to setup HTTPS:
1. Open Tab Labeled "Security"
2. Select Tab Labeled "Email/SSL"
3. Scroll to bottom under "SSL Settings"
4. Click "Select Certificate"
5. Browse and select valid Certificate to upload from server
6. Click "Select Key"
7. Browse and select valid Key to upload from server
8. Click "Submit Files"
Once the Certificate and Key is uploaded successfully you can proceed with setting up
HTTPS in Network Settings.
A. HTTPS Port: Enter the HTTPS port number assigned to the LINQ8PD(CB) module by the network
administrator to allow remote access and monitoring. The default inbound port setting is 443.
Being encrypted and more secure, HTTPS is highly recommended for remote access.
B. Click the button labeled Submit Network Settings.
A dialog box will display "New network settings will take effect after the server is rebooted". Click OK.
When not using the Altronix Dashboard USB connection for the initial Network setup the LINQ8PD(CB) needs
to be connected to any DC power supply(ies) or eFlow power supply(ies) being monitored (refer to Installing
LINQ8PD(CB) Board on page 2 of these instructions) prior to programing.
Factory Default settings
• IP Address:
• User Name:
• Password:
1. Set the static IP address for the laptop to be used for programming to the same network IP address as the
LINQ8PD(CB), i.e. 192.168.168.200 (default address of the LINQ8PD(CB) is 192.168.168.168).
2. Connect one end of the network cable to the network jack on the LINQ8PD(CB) and the other to the network
connection of the laptop.
3. Open a browser on the computer and enter "192.168.168.168" into the address bar.
A dialog box Authentication Required will appear requesting both user name and password.
Enter the default values here. Click on the button labeled Log In.
4. The status page of the LINQ8PD(CB) will appear. This page displays the real time status and health of each
power supply connected to the LINQ8PD(CB).
LINQ8PD / LINQ8PDCB Installation and Programming Manual

Browser Setup:

192.168.168.168
admin
admin