Siemens SENTRON PAC3200T Product Manual page 82

7km power monitoring device
Hide thumbs Also See for SENTRON PAC3200T:
Table of Contents

Advertisement

Technical data
8.1 Technical data
Digital output
Digital output
Number
Type
Design/function
Maximum switching voltage
Output current
Internal resistance
Overvoltage category
Pulse output function
Max. switching frequency
Short-circuit protection
Communication
Ethernet interface
Ethernet
Ethernet connection
Data rate
Autocrossover
Autonegation
Connection elements
Power connection: IL1, IL2, IL3
Conductor cross-section for copper cable (Cu)
Rigid
Flexible
Flexible with end sleeve, without plastic
sleeve
Flexible with end sleeve and plastic
sleeve
Tightening torque
80
For signal "1"
Continuous load
Transient overload
For signal "0"
Standard for pulse emitter
Adjustable pulse duration
Min. settable time frame
1
Passive
Switching output or pulse output
30 V
Depends on the load and the external power
supply
≤50 mA (thermal overload protection)
≤130 mA for 100 ms
≤0.2 mA
30 Ω
CAT I
Signal characteristics in accordance with
IEC 62053-31
30 ... 500 ms
10 ms
17 Hz
Yes
Modbus TCP; web server (HTTP); SNTP; DHCP
RJ-45
10/100 Mbps
Available
Available
mm
2
1 x 0.2 ... 6.0
1 x 0.2 ... 4.0
1 x 0.2 ... 4.0
1 x 0.25 ... 4.0
0.5 ... 0.6 Nm
[4.4 ... 5.3 lb-in]
Equipment Manual, 09/2022, L1V30415168B-03
AWG
1 x 24 ... 10
1 x 24 ... 12
1 x 24 ... 12
1 x 24 ... 12

Hide quick links:

Advertisement

Table of Contents
loading