A.1 Modbus TCP
A.1.12

Modbus device information with the function codes 0x03, 0x04 and 0x10

Addressing the device information parameters
You access the following device information parameters block-by-block only, e.g. read from
Offset 64001 27 Register.
Note
Error in the case of inconsistent access to I&M data.
Please ensure the start offset and the number of registers are correct when making read
accesses and write accesses. Always read or write the entire block.
Please ensure the start offset and the number of registers are correct when making write
accesses.
If a value consists of several registers, a read command applied in the second register, for
example, will generate an error code. The PAC3200T will also output an error code if, for
example, a write operation ends in the middle of a multi-register value.
Table A- 14
I&M 0 parameters with the function codes 0x03 and 0x04
Offset
Total
registers
Start offset
27
64001
[64002]
[64012]
[64020]
[64021]
[64023]
[64024]
[64025]
[64026]
[64027]
*) 42 stands for Siemens AG
128
Number of
Name
registers per
parameter
[1]
Manufacturer's ID
[10]
Order No.
[8]
Serial number
[1]
Hardware version
[2]
Firmware version
[1]
Counter for changes
[1]
Profile ID
[1]
Specific Profile ID
[1]
Version of the I&M data 2 unsigned char
[1]
Supported I&M data
Format
Value range
unsigned short
42
*)
Char 20
ASCII
Char 16
ASCII
unsigned short
0 ... 65535
1 char, 3 unsigned
V 0.0.0 ...
char
V 255.255.255
unsigned short
1 ... 65535
unsigned short
3A00 ... F6FF
unsigned short
-
0.0 ... 255.255
unsigned short
00 ... FF
Equipment Manual, 09/2022, L1V30415168B-03
Access
R
R
R
R
R
R
R
R
R
R