Pump control and monitoring unit with display for either 1 or 2 pumps. display in steel housing for 1 or 2 pumps. LevelControl Basic 2 can be used for tank drainage and tank Level detection performed using at least filling.
Without PTC relay for > 4 kW versions (standard for 5.5 kW and above) Without PTC relay for > 4 kW versions (standard for 5.5 kW and above), with rechargeable battery Nominal current 1,0 A 1,6 A 2,5 A 4,0 A 6,3 A 10 A 14 A 18 A 23 A 25 A Higher ratings on request. LevelControl Basic 2...
Outdoor installation: ▪ Control units installed outdoors (e.g. in outdoor cabinets) should always be equipped with Type 1 surge protective devices (lightning protection), as they will not normally be protected by a suitable upstream service entrance SPD. LevelControl Basic 2...
The control unit is selected on the basis of the nominal current of the pump. Higher currents and power ratings are available on request. The standard variant of LevelControl Basic 2 is not suitable for use in IT mains. Variants for IT mains are available on request. For the following special voltages (3~ only) LevelControl Basic 2 can be configured via KSB EasySelect: ▪...
Pump Switchgear / Control Systems LevelControl Control Units LevelControl Basic 2 for Ama-Drainer Documented device versions Control units for single-pump station Size Float switch incl. 4 - 20 mA input Pneumatic DFNO SFNO DPNO SPNO DFNO DPNO 230 V: up to 10 A...
Page 10
✘ Remote acknowledgement ✘ ✘ 12 V DC connection for horn, etc. ✘ ✘ Sensor accessories Float switch (NO contact) Redundant high water float switch Open pressure bell Closed pressure bell F1 leakage sensor Tools KSB ServiceTool for Windows XP LevelControl Basic 2...
Page 11
High-water float switch Base load ON mini-Compacta/Compacta sensors Pumps OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic 230 V bk (black) bu (blue) bn (brown) PE: gn/ye (green/yellow) Pump 1 LevelControl Basic 2...
Page 12
Base load ON mini-Compacta/Compacta sensors Pumps OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic 400 V U1: bk (black) V1: bu (blue) W1: bn (brown) PE: gn/ye (green/yellow) Pump 1 LevelControl Basic 2...
Page 13
Sensors for mini-Compacta/Compacta Pumps OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic 400 V U1: bk (black) V1: bu (blue) W1: bn (brown) PE: gn/ye (green/yellow) Pump 1 LevelControl Basic 2...
Pump Switchgear / Control Systems LevelControl Control Units LevelControl Basic 2 for Ama-Porter Documented device variants Control units for single-pump station Size Float switch Pneumatic Bubbler control incl. 4 - 20 mA input DFNO DPNO DLNO in BS housing DLNO in BC housing...
Page 15
✘ Remote acknowledgement ✘ ✘ 12 V DC connection for horn, etc. ✘ ✘ Sensor accessories Float switch (NO contact) Redundant high water float switch Open pressure bell Closed pressure bell F1 leakage sensor Tools KSB ServiceTool for Windows XP LevelControl Basic 2...
Page 16
Base load ON Sensors for mini-Compacta/Compacta Pump OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic 230 V bk (black) bu (blue) bn (brown) PE: gn/ye (green/yellow) Pump 1 LevelControl Basic 2...
Page 17
Sensors for mini-Compacta/Compacta Pump OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic 400 V U1: bk (black) V1: bu (blue) W1: bn (brown) PE: gn/ye (green/yellow) Pump 1 LevelControl Basic 2...
Pump Switchgear / Control Systems LevelControl Control Units LevelControl Basic 2 for Amarex / Amarex N Non-ATEX-compliant versions Documented device versions Control units for single-pump station, non-ATEX-compliant Size Float switch Pneumatic Bubbler control incl. 4-20 mA input DFNO DPNO DLNO in BS housing...
Page 19
✘ Remote acknowledgement ✘ ✘ 12 V DC connection for horn, etc. ✘ ✘ Sensor accessories Float switch (NO contact) Redundant high water float switch Open pressure bell Closed pressure bell F1 leakage sensor Tools KSB ServiceTool for Windows XP LevelControl Basic 2...
Page 20
Analog intrinsic safety barriers are required in ATEX- compliant versions for 4 - 20 mA (see Optional components). The control units are not explosion-proof, which means Selection via KSB EasySelect. that they must not be operated in potentially explosive atmospheres. Documented device versions...
Page 21
✘ 12 V DC connection for horn, etc. ✘ ✘ Sensors Float switch (NO contact) Open pressure bell Closed pressure bell Tools KSB ServiceTool for Windows XP Additional intrinsic safety barrier required for high water float switch (see Optional components) LevelControl Basic 2...
Page 22
Float switch / digital level switch Pump ON/OFF High-water float switch Base load ON Sensors for mini-Compacta/Compacta Pump OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic Pump connection Pump 1 LevelControl Basic 2...
Page 23
Float switch / digital level switch Pump ON/OFF High-water float switch Base load ON Sensors for mini-Compacta/Compacta Pump OFF Connection for alarm equipment Signal transmitter 12 V External alarm input Contact Remote acknowledgement Rechargeable battery connection Pneumatic Pump connection Pump 1 LevelControl Basic 2...
Pump Switchgear / Control Systems LevelControl Control Units LevelControl Basic 2 for Amarex KRT Documented device versions Control units for single-pump station, ATEX-compliant version Size Float switch Float switch Pneumatic Bubbler control incl. 4 - 20 mA input xFNO xFEO (ATEX-compliant) xPEO (ATEX-compliant)
Page 25
Open pressure bell Closed pressure bell Tools KSB ServiceTool for Windows XP Additional intrinsic safety barrier required for high water float switch (see Optional components) Analog intrinsic safety barriers are required in ATEX-compliant versions for 4 - 20 mA (see Optional components). Selection via KSB EasySelect.
Page 26
Pump Switchgear / Control Systems LevelControl Control Units Amarex KRT with control unit type BS, from 5.5 kW Amarex KRT Fig. 8: Circuit diagram: Amarex KRT LevelControl Basic 2...
Page 27
Float switch / digital switch Peak load ON High-water float switch Pump ON/OFF Sensors for mini-Compacta/Compacta Base load ON Connection for alarm equipment Pumps OFF External alarm input Signal transmitter 12 V Remote acknowledgement Contact Pneumatic Rechargeable battery connection LevelControl Basic 2...
▪ Amarex N - non-ATEX-compliant version Control panel Volt-free contact Master switch (optional) Mains supply Manual-0-automatic switch Contactors (pump connection) Control board Motor protection switch (pumps) Digital inputs, 4 .. 20 mA, 12 V for horn, etc. Rechargeable battery (optional) LevelControl Basic 2...
Page 29
Master switch 12 V for horn, etc. Control panel Contactors (pump connection) Manual-0-automatic switch Mains supply Control transformer Compressor Rechargeable battery (optional) Connection for open pressure bell Control electronics Motor protection switch (control circuit) Motor protection switch (pumps) LevelControl Basic 2...
Page 30
Control panel Contactors (pump connection) Manual-0-automatic switch Mains supply Control transformer Connection (float switch, digital level switch) via intrinsic safety barriers Rechargeable battery (optional) Motor protection switch (control circuit) Control electronics Motor protection switch (pumps) Intrinsic safety barrier LevelControl Basic 2...
LevelControl Basic 2 for 230 V is designed with sockets on the side wall (connection of the pump/s). To make sure the connections can be made at the plugs, outdoor cabinets for this version are selected one size larger than usual. LevelControl Basic 2 for outdoor installation: Type BC: Using a heater is recommended.
Signalling module for type BS, with pressure sensor 10 mWC for redundant pneumatic level 19075187 measurement Processed via KSB EasySelect, to avoid supply as unmounted item. The initial scope of supply is configured via KSB EasySelect; when retrofitting check beforehand whether there is sufficient space in the control cabinet. LevelControl Basic 2...
Page 33
0,15 Can only be used in combination with signalling O211 Measuring range: 10 - 20 A (30 A) 19075189 0,15 module O212 Measuring range: 20 - 40 A (60 A) 19075190 0,15 O213 Measuring range: 40 - 75 A (110 A) 19075191 0,15 LevelControl Basic 2...
Page 34
Plastic handle with safety cylinder insert for KS wall-mounted cabinet (O14) 01855128 0,086 Order 2 pieces for KS cabinet. The initial scope of supply is configured via KSB EasySelect; when retrofitting check beforehand whether there is sufficient space in the control cabinet. LevelControl Basic 2...
Page 35
Operating manual in Estonian 01802910 0,155 Operating manual in Portuguese For additional copies. The operating manual and the parameter label are enclosed with the device. The operating manual can be downloaded free of charge from the KSB website (www.ksb.com). LevelControl Basic 2...