 Power supply
Choose a power supply for encoder according to the encoder used (5 V/12 V/15 V/24 V). When the encoder output is the
differential line driver type, only 5 V can be input. Make sure the voltage of the external power supply the same as the encoder
output voltage. (Check the encoder specification.)
When an encoder is used under orientation control, encoder feedback control, and vector control, the power supply is shared
between the inverter and encoder.
• Specifications of the encoders equipped in the motors with encoders and the vector-control dedicated motors
Item
Resolution
Power supply voltage
Current consumption
Output signal form
Output circuit
Output voltage
NOTE
• When the input power supply voltage to the encoder and its output voltage differ, the protective function (E.ECT) may be
activated.
 Parameters for encoder
For the parameters for encoder, refer to the FR-A800 Instruction Manual (Detailed).
Encoder for SF-PR-SC/SF-V5RU/SF-THY
2048 pulses/rev
12 VDC ±10%, 24 VDC ±10%
90 mA
A, B phases (90° phase shift)
Z phase: 1 pulse/rev
Complementary
H level: "Power supply for encoder-3 V" or more
L level: 3 V or less
ENCODER SPECIFICATIONS AND PARAMETER SETTINGS
Encoder for SF-JR/HR/JRCA/HRCA
1024 pulses/rev
5 VDC±10%
60 mA or less
Equivalent to differential line driver
AM26LS31
H level: 2.4 V or more
L level: 0.5 V or less
3
27