10.8 - Other options

Options
No.
Corrosion protection,
3A
traditional coils
Low-temperature brine
6B
solution
Unit equipped for air
12
discharge ducting
Low noise level
15
Very low noise level
15LS
IP54 control box
20A
Protection grilles
23
Enclosure panels
23A
Soft Starter
25
Winter operation down to
28
-20°C
Water exchanger frost
41
protection
Exchanger & hydraulic frost
42A
protection
Partial heat recovery
49
Master/slave operation
58
Compressor discharge
93A
valves
HP single-pump hydronic
116R
module
HP dual-pump hydronic
116S
module
LP single-pump hydronic
116T
module
LP dual-pump hydronic
116U
module
HP variable-speed single-
116V
pump hydraulic mod.
HP variable-speed dual-
116W Dual high-pressure water pump with variable speed drive (VSD),
pump hydraulic mod.
J-Bus gateway
148B
Lon gateway
148D
Bacnet over IP gateway
149
Energy Management
156
Module
Conformance with Russian
199
regulations
Compliance with Australian
200
regulations
Coil defrost resistance
252
heaters
Welded water exchanger
266
connection kit
230V electrical plug
284
Safety hydraulic
293
components, evap. side
Welded desuperheater
303
BPHE water connection kit
Screwed desuperheater
304
BPHE water connection kit
Set point adjustment by
311
4-20mA signal
Description
Fins made of pre-treated aluminium (polyurethane and epoxy)
Low temperature chilled water production down to -8°C
with ethylene or propylene glycol
Unit equipped with high static variable-speed fans (maximum
200 Pa), each fan equipped with a connection flange allowing
the connection to the ducting system.
Aesthetic and sound absorbing compressor enclosure
Aesthetic and sound absorbing compressor enclosure associated
with low-speed fans
Increased leak tightness of electrical box
Metallic protection grilles
Side enclosure panels at each end of the coil
Electronic starter on each compressor
Fan speed control of lead fan for each circuit using a variable
frequency drive
Electric heater on the water exchanger and the water piping
Electric heater on the water exchanger hydronic module and
optional expansion tank
Partial heat recovery by desuperheating of the compressor
discharge gas.
Unit equipped with supplementary water outlet temperature
sensor kit to be field-installed allowing master/slave operation of
two units connected in parallel
Shut-off valve on the compressor discharge piping
Single high-pressure water pump, water filter, electronic water
flow control, pressure transducers. See hydraulic module option
chapter
Dual high-pressure water pump, water filter, electronic water
flow control, pressure transducers. See hydraulic module option
chapter
Single low-pressure water pump, water filter, electronic water
flow control, pressure transducers. See hydraulic module option
chapter
Dual low-pressure water pump, water filter, electronic water
flow control, pressure transducers. See hydraulic module option
chapter
Single high-pressure water pump with variable speed drive (VSD),
water filter, electronic water flow control, pressure transducers.
Multiple possibilities of water flow control. See hydraulic module
option chapter
water filter, electronic flow switch, pressure transducers. Multiple
possibilities of water flow control. See hydraulic module option
chapter
Two-directional communication board complying with JBus
protocol
Two-directional communication board complying with Lon Talk
protocol
Two-directional high-speed communication using BACnet
protocol over Ethernet network (IP)
Control board with additional inputs/outputs. See Energy
Management Module option chapter
EAC certification
Unit approved to Australian code
Electric heaters under the coils and the condensate pans
Victaulic piping connections with welded joints
230V AC power supply source provided with plug socket and
transformer (180 VA, 0,8 Amps)
Screen filter, expansion tank and relief valve integrated in the
evaporator hydronic module
Victaulic piping connections with welded joints for the
desuperheater exchanger
Victaulic piping connections with screwed joints for the
desuperheater exchanger
Connections to allow a 4-20mA signal input
Advantages
Improved corrosion resistance, recommended for moderate
marine and urban environments
Covers specific applications such as ice storage and
industrial processes
Ducted fan discharge, optimised condensing or evaporating
temperature control, based on the operating conditions and
system characteristics
Noise level reduction by 1 to 2 dB(A)
Noise level reduction for sensible site
Protects the inside of the electrical box from dusts and sand. In
general this option is recommended for installations in polluted
environments
Coil protection against possible shocks
Improves aesthetics, coil and piping protection against impacts. 30RQM/30RQP
Reduced start-up current
Stable unit operation for outside air temperature from 0°C down
to -20°C in cooling mode
Water exchanger module frost protection between 0°C and -20°C
outside air temperature
Water exchanger and hydraulic module frost protection between
0°C and -20°C outside air temperature
Free high-temperature hot-water production simultaneously with
chilled and hot-water production
Optimised operation of two heat-pumps connected in parallel with
operating time equalisation
Simplified maintenance
Easy and fast installation (plug & play)
Easy and fast installation (plug & play)
Easy and fast installation (plug & play)
Easy and fast installation (plug & play)
Easy and fast installation (plug & play), significant pumping energy
cost savings (more than two-thirds), tighter water flow control,
improved sytem reliability
Easy and fast installation (plug & play), significant pumping energy
cost savings (more than two-thirds), tighter water flow control,
improved sytem reliability
Connects the unit by communication bus to a building
management system
Connects the unit by communication bus to a building
management system
Easy and high-speed connection by ethernet line to a building
management system. Allows access to multiple unit parameters
Extended remote control capabilities (Set-point reset, ice storage
end, demand limits, boiler on/off command...)
Conformance with Russian regulations
Conformance with Australian regulations
Prevents frost formation on the coils; compulsory in the heating
mode, if the outdoor is below 0°C
Easy installation
Permits connection of a laptop or an electrical device during unit
commissioning or servicing
Easy and fast installation, operating safety
Easy installation
Easy installation
Easy energy managment, allow to adjust set point by a 4-20mA
external signal
Use
30RQM/30RQP
160-520
30RQP
180-230-270-310
30RQP 160-520
30RQM/30RQP
160-520
30RQP 160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
160-520
30RQM/30RQP
160-520
30RQM 160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
30RQM/30RQP
160-520
55