IMPORTANT: Never use a pressure water spray without a large
diffuser. Concentrated and/or rotating water jets are strictly
prohibited.
Never use a fluid with a temperature above 45°C to clean the
air heat exchangers.
Correct and frequent cleaning (approximately every three
months) will prevent two-thirds of corrosion problems. Protect
the electrics box during cleaning operations.

11.7 - Water heat exchanger maintenance

Check that:
The insulation has not been detached or torn during
operations,
The heaters and probes are operating and correctly
positioned in their support,
The water-side connections are clean and show no sign of
leakage,
The period inspections required by the local regulations
have been carried out.

11.8 - Variable frequency drive maintenance

CAUTION: Before any work on the variable drive, ensure that
the circuit is isolated and there is no voltage present (reminder:
capacitor discharge time: approximately 5 minutes after the
circuit breaker is opened). Only appropriately qualified
personnel are authorised to work on the variable frequency
drive.
In case of any alarm or persistent problem related to the variable
frequency drive, contact Carrier Service.
The variable drives fitted on 30RQM/30RQP units do not require
a dielectric test, even if being replaced: they are systematically
verified before delivery. Moreover, the filtering components
installed in the variable drive can falsify the measurement and
may even be damaged. If it is necessary to test the insulation of
the unit components (fan motors and pumps, cables, etc.), the
variable frequency drive must be disconnected from the power
circuit.
58

11.9 - Characteristics of R-410A

See the table below.
Saturated temperatures based on the gauge pressure (in kPa)
Pressure
Pressure
Saturated
Saturated
Temp.
Temp.
gauge
gauge
-20
297
4
807
-19
312
5
835
-18
328
6
864
-17
345
7
894
-16
361
8
924
-15
379
9
956
-14
397
10
987
-13
415
11
1020
-12
434
12
1053
-11
453
13
1087
-10
473
14
1121
-9
493
15
1156
-8
514
16
1192
-7
535
17
1229
-6
557
18
1267
-5
579
19
1305
-4
602
20
1344
-3
626
21
1384
-2
650
22
1425
-1
674
23
1467
0
700
24
1509
726
1596
1
26
2
752
25
1552
3
779
27
1641
Aquasnap units use high pressure R-410A refrigerant (the unit
operating pressure is above 40 bar, the pressure at 35°C air
temperature is 50% higher than for R-22). Special equipment
must be used when working on the refrigerant circuit (pressure
measurement, charge transfer, etc.).

11.10 - Check of power factor correction capacitors

The verification consists in measuring input current of each
capacitor bank. Check shall be done using a true RMS meter
reading:
Check per phase current delivered by each capacitor and
compare it to nominal values. In case of capacitance losses or
unbalance, the capacitors must be replaced.
Ensure that the current through the capacitor doesn't exceed
1.3xIr. A higher value may indicate heavy presence of harmonics,
that will impact the lifetime of the capacitor.
Absence of current despite capacitor is energized is an indication
that there is a defect. Confirmation shall be done by removing
the capacitors and checking the underside
Faulty
Pressure
Pressure
Saturated
Saturated
Temp.
temp.
gauge
gauge
28
1687
52
3088
29
1734
53
3161
30
1781
54
3234
31
1830
55
3310
32
1880
56
3386
33
1930
57
3464
34
1981
58
3543
35
2034
59
3624
36
2087
60
3706
37
2142
61
3789
38
2197
62
3874
39
2253
63
3961
40
2311
64
4049
41
2369
65
4138
42
2429
66
4229
43
2490
67
4322
44
2551
68
4416
45
2614
69
4512
46
2678
70
4610
47
2744
48
2810
2878
49
50
2947
51
3017
Correct

Advertisement

Table of Contents
loading

Table of Contents