4.6 - Electrical data notes for the hydraulic module

The pumps that are factory-installed in these units have motors with efficiency class IE3. The additional electrical data required
is as follows:
For the low pressure single pump motors for 30RQM/30RQP 160-520 units (option 116T)
No.
Description
(2)
(3)
1
Nominal efficiency at full load and nominal voltage
1
Nominal efficiency at 75% full load and nominal voltage
1
Nominal efficiency at 50% full load and nominal voltage
2
Efficiency level
3
Year of manufacture
4
Manufacturer's name or trademark, commercial registration number
and registered address
5
Product's model number
6
Number of motor poles
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
7-2
Maximum input power (400 V)
8
Nominal input frequency
9-1
Nominal voltage
9-2
Maximum current drawn (400 V)
10
Nominal speed
11
Product disassembly, recycling or disposal at end of life
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
II - Ambient air temperature
III - Maximum operating temperature
IV - Potentially explosive atmospheres
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current draw.
For the low pressure dual-pump motors for 30RQM/30RQP 160-520 units (option 116U)
No.
Description
(2)
(3)
1
Nominal efficiency at full load and nominal voltage
1
Nominal efficiency at 75% full load and nominal voltage
1
Nominal efficiency at 50% full load and nominal voltage
2
Efficiency level
3
Year of manufacture
4
Manufacturer's name or trademark, commercial registration number
and registered address
5
Product's model number
6
Number of motor poles
7-1
Nominal shaft power output at full load and nominal voltage (400 V)
7-2
Maximum input power (400 V)
8
Nominal input frequency
9-1
Nominal voltage
9-2
Maximum current drawn (400 V)
10
Nominal speed
11
Product disassembly, recycling or disposal at end of life
12
Operating conditions for which the motor is specifically designed
I - Altitudes above sea level
II - Ambient air temperature
III - Maximum operating temperature
IV - Potentially explosive atmospheres
(1) Additional electrical data required by regulation No. 640/2009 concerning the application of directive 2005/32/EC on the eco-design requirements for electric motors.
(2) Item number imposed by regulation No. 640/2009, annex I2b.
(3) Description given by regulation No. 640/2009, annex I2b.
(4) Above 1000 m, a degradation of 3% for each 500 m should be taken into consideration.
(5) To obtain the maximum input power for a unit with hydraulic module, add the maximum unit input power from the electrical data table to the pump power input.
(6) To obtain the maximum unit operating current draw for a unit with hydraulic module add the maximum unit current draw from the electrical data table to the pump current draw.
20
(5)
(6)
(5)
(6)
Units
30RQM/30RQP
160
180
210
230
%
86.4 86.4 86.4 86.4 87.5 87.5 87.5 89.6 89.6 89.6 89.7
%
86.9 86.9 86.9 86.9 88.2 88.2 88.2 90.4 90.4 90.4 90.0
%
85.7 85.7 85.7 85.7 87.5 87.5 87.5 89.9 89.9 89.9 89.0
-
IE3
-
This information varies depending on the manufacturer and model at the time
of incorporation. Please refer to the motor nameplates.
-
Same as above
-
Same as above
-
2
2
2
2
kW
2.2
2.2
2.2
2.2
kW
2.80 2.80 2.80 2.80 3.81 3.81 3.81 4.96 4.96 4.96 6.80
Hz
50
50
50
50
V
3 x
400
A
4.92 4.92 4.92 4.92 6.81 6.81 6.81 8.27 8.27 8.27 11.30 11.30
r/s - r/min
48 - 2900
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
m
< 1000
(4)
°C
< 40
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the Carrier selection programs.
-
Non ATEX environment
Units
30RQM/30RQP
160
180
210
230
%
85.9 86.4 87.5 87.5 87.5 87.5 87.5 89.6 89.6 89.6 89.7
%
86.4 86.9 88.2 88.2 88.2 88.2 88.2 90.4 90.4 90.4 90.0
%
84.9 85.7 87.5 87.5 87.5 87.5 87.5 89.9 89.9 89.9 89.0
-
IE3
-
This information varies depending on the manufacturer and model at the time
of incorporation. Please refer to the motor nameplates.
-
Same as above
-
Same as above
-
2
2
2
2
kW
1.5
2.2
3
3
kW
1.94 2.80 3.81 3.81 3.81 3.81 3.81 4.96 4.96 4.96 6.80
Hz
50
50
50
50
V
3 x 400
A
3.41 4.92 6.81 6.81 6.81 6.81 6.81 8.27 8.27 8.27 11.30 11.30
r/s - r/min
48 - 2900
-
Disassembly using standard tools. Disposal and recycling using an appropriate
company.
m
< 1000
(4)
°C
< 40
°C
Please refer to the operating conditions given in this manual or in the specific
conditions in the Carrier selection programs.
-
Non ATEX environment
240
270
310
330
380
430
2
2
2
2
2
2
3
3
3
4
4
4
50
50
50
50
50
50
240
270
310
330
380
430
2
2
2
2
2
2
3
3
3
4
4
4
50
50
50
50
50
50
(1)
470
520
89.7
90.0
89.0
2
2
5.5
5.5
6.80
50
50
470
520
89.7
90.0
89.0
2
2
5.5
5.5
6.80
50
50

Advertisement