10.6.2.3 PROFIBUS Interface
The sensor option profibus is fitted as standard with a profibus interface according to IEC61158 / IEC61784.
The following parameters are specified.
Table 10: Parameter PROFIBUS Interface
PROFIBUS Interface
Transmission
Wire length
Baud rate
Clock rate max.
Participants
10.6.2.4 Pin Assignment
Table 11: Pin Assignment PROFIBUS IN
PROFIBUS IN (Flanged Plug M12)
Pin
1
2
3
4
5
Table 13: Power Supply
Power supply (Fanged Plug M8)
Pin
1
2
3
4
Profibus OUT
Power Supply
Figure 35: Pin Assignment PROFIBUS
RS485 two-wire line
1200 m at 9,6 kBaud
200 m at 1,5 MBaud
100 m at 12 MBaud
9,6 kBaud to 12 MBaud (auto detect)
250 kHz
max. 32 per Segment (with repeater until 126 expandable)
Mono- and Multi-master systems are possible
 In delivery status is participant 05 set
Function
N.C.
Data A
N.C.
Data B
Shield
Color
Brown
White
Blue
Black
- 37 -
Table 12: Pin Assignment PROFIBUS OUT
PROFIBUS OUT (Flanged Socket M12)
Pin
1
2
3
4
5
Function
+ 10 to 30 VDC
N.C.
0 V / GND
N.C.
Connections and Interfaces
Function
N.C.
Data A
N.C.
Data B
Shield