Mitsubishi Electric CITY MULTI PDFY Series Technical & Service Manual page 17

Ceiling concealed built-in, indoor unit
Table of Contents

Advertisement

Switch Pole
Function
Thermistor<Intake temperature
1
detection>position
2
Filter crogging detection
3
Filter life
4
Air intake
SW1
5
Remote indication switching
Mode
6
Humidifier control
Selection
7
Air flow st
8
Heat thermostat OFF
9
Auto reset function
10
Power ON/OFF
MODELS
PDFY-
P06NMU-E
SW2
Capacity
PDFY-
1~6
P08NMU-E
code
setting
PDFY-
P12NMU-E
PDFY-
P15NMU-E
MODELS
SW3
PDFY-
Function
1~10
P06,08,12,18,24,27,
Selection
30,48NMU-E
SW4
P06~30
Unit
ON
1~4
OFF
Selection
Note
:The DipSW setting is effective during unit stopping ( remote controller OFF ) for SW1,2,3 and 4 commonly and the
power source is not required to reset.
16
ON
Built-in remote controller
Provided
2,500hr
Effective
Thermostat ON signal indication Fan output indication
Always operated while the heat is ON
Low
Setting air flow
Effective
Effective
SW2
MODELS
ON
ON
PDFY-
OFF
OFF
P18NMU-E
1 2 3 4 5 6
ON
ON
PDFY-
OFF
OFF
P24NMU-E
1 2 3 4 5 6
ON
ON
PDFY-
OFF
OFF
P27NMU-E
1 2 3 4 5 6
ON
ON
PDFY-
OFF
OFF
P30NMU-E
1 2 3 4 5 6
SW3
ON
OFF
1 2 3 4 5 6 7 8 9 10
P36,48
ON
OFF
1 2 3 4
Operation by switch
OFF
Indoor unit
Not provided
100hr
Not effective
Operated depends on the condition
Extra low
Reset to SW1-7
Not effective
Not effective
SW2
MODELS
ON
PDFY-
OFF
P36NMU-E
1 2 3 4 5 6
ON
PDFY-
OFF
P48NMU-E
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
MODELS
SW3
PDFY-P15,36
ON
OFF
NMU-E
1 2 3 4 5 6 7 8 9 10
<At delivery>
1 2 3 4 5
Remarks
Address board
<At delivery>
ON
OFF
Indoor controller board
SW2
Set while the unit is off.
<At delivery>
1 2 3 4 5 6
Set for each capacity.
1 2 3 4 5 6
Indoor controller board
Set while the unit is off.
Indoor controller board
Set while the unit is off.
1 2 3 4 5 6 7 8 9 10